3
UK
3 Installation
► Mount the devices on a 35 mm rail.
1
2
3
4
Example DF12xx circuit protection module
1: rail
2: contact lever
3: installation area
4: operating area
4 Electrical connection
► Dimension cables according to input and output current.
► Insert wires directly into the terminals as shown on the device label.
Art. no.
Terminals
Potential
Cross-
section
[mm²]
Stripping
length
[mm]
DF11xx
24 V DC
supply
0.5...10
18
0 V
0.14...2.5
8...10
13-14
NO contacts
0.14...2.5
8...10
DF12xx
O1 or O1/O2
current outputs
0.14...2.5
8...10
To disconnect press the orange pusher using a suitable tool.
To open the push-in terminals IO-Link use a 2 mm wide micro screwdriver.
As soon as the supply module is supplied with voltage, the device closes
the contacts connected to terminals 13 and 14. If a fault occurs at min. one
of the connected channels, the device opens the contacts again.