8  Parameter setting

Automatic saving of the communication and unit parameters can be activated or 

deactivated by means of the "save all parameters" entry (see object directory, 

index 1010)� When the value 0x02 is entered into SIdx 01, all parameters are auto-

matically saved if changes were made�
With the value 0x00 there is no automatic saving, i�e� changed parameters will only 

be valid until the unit is switched off or until the next reset is made�
With the function "restore" (see object directory, index 1011) the parameters 

(except the baud rate and the node ID) can be assigned to the factory default val- 

ues� With the next power on they become valid�

8.1  Parameter list

Parameter

Index in ob-

ject directory

Default  

(factory preset)

Change automati-

cally saved

Change  

effective

Manufacturer Specific Profile Area; index 2000 to 5FFF
I/O Configuration

2000

binary inputs/

outputs

adjustable

after PreOp

PWM Frequency

2001

0x64 (100Hz)

adjustable

after PreOp

Node ID *)

20F0, 20F1

0x20 (0d32)

yes

after a reset

Baud rate *)

20F2, 20F3

0x04 (125 Kbits/s)

yes

after a reset

Communication Profile Area; Index 1000 to 1FFF
COB ID Synch Objekt

1005

0x80

adjustable

after a reset

Communication Cycle

1006

0x00 (Off)

adjustable

immediately

Guard Time

100C

0x00 (Off)

adjustable

immediately

Life Time Factor

100D

0x00

adjustable

immediately

Save Parameter

1010

0x02 

(AutoSave ON)

yes

immediately

COB ID EMCY

1014

0x80 + Node ID

adjustable

after a reset

Consumer 

Heartbeat time

1016

0x00 (Off)

adjustable

immediately

Producer  

Heartbeat time

1017

0x00 (Off)

adjustable

immediately

COB ID Rec PDO 1

1400 01

0x200 + Node ID

adjustable

after a reset

Trans Type Rec PDO 1

1400 02

0x01 (synchronous) adjustable

immediately

COB ID Rec PDO 2

1401 01

0x300 + Node ID

adjustable

after a reset

Trans Type Rec PDO 2

1401 02

0x01 (synchronous) adjustable

immediately

COB ID Trans PDO 1

1800 01

0x180 + Node ID

adjustable

after a reset

Trans Type Trans PDO 1

1800 02

0xFF (asynchro-

nous)

adjustable

immediately

Summary of Contents for CompactModule CR2032

Page 1: ...Device manual Input output module CompactModule metal CR2032 80269922 00 01 2018 UK...

Page 2: ...Fuses 6 6 7 Examples types of connection 7 7 Set up 8 7 1 PLC configuration in CODESYS 2 3 8 7 2 PLC configuration in CODESYS 3 5 9 7 2 1 Heartbeat configuration 9 7 2 2 SyncMonitoring 10 7 3 Electron...

Page 3: ...d output load circuits If the unit is not supplied by the mobile on board system 12 24 V battery opera tion it must be ensured that the external voltage is generated and supplied ac cording to the cri...

Page 4: ...reak and short circuit PWM outputs up to 2 A There are 1 server SDO and the 4 default PDOs to CiA DS 401 The PDO mapping cannot be changed static PDO mapping The default iden tifiers are assigned acco...

Page 5: ...and sealing For normal corrosive requirements zinc plated screws are sufficient 6 Electrical connection To guarantee the electrical interference protection of the module the hou sing must be connecte...

Page 6: ...current IN 2 A 100 overload 4 A Test duration 5 minutes 6 5 CAGE CLAMP connection technology 1 2 1 Screw driver 2 Wire Insert screw driver and tilt slightly spring opens Insert wire Remove screw drive...

Page 7: ...UK CompactModul Metall CR2032 7 6 7 Examples types of connection Example 1 Example 2 Example 3 Example 4 jumper inserted...

Page 8: ...erface is directly done from the application programmed with CODESYS 2 3 To do so the Electronic Data Sheet EDS is integrated via the CODESYS PLC configuration CODESYS dialogue PLC configuration examp...

Page 9: ...te Device and click on In stall Select EDS file and click on Open In CODESYS 3 5 the devices are integrated as CiA remote devices in the de vice tree under a CANopen_Manager element The CANopen commun...

Page 10: ...lementing the SDO list in the CANopen configurator or during the operating time via the function block COP_SDOwrite The monitoring time is indicated in microseconds s 7 3 Electronic Data Sheet The EDS...

Page 11: ...inputs outputs adjustable after PreOp PWM Frequency 2001 0x64 100Hz adjustable after PreOp Node ID 20F0 20F1 0x20 0d32 yes after a reset Baud rate 20F2 20F3 0x04 125 Kbits s yes after a reset Communic...

Page 12: ...e time factor 0 is interpreted as 1 The first guard protocol is assessed as start guarding even if guarding is not active at this time guard time 0 Observe the position of the hex code switch Entries...

Page 13: ...and UB potentials linked upon delivery Cable entry via M16 cable gland Inputs Outputs 8 x M12 connector socket 5 pole CANin CANout 2 x M12 connector plug socket 5 pole Weight 1 35 kg Inputs 8 can be...

Page 14: ...ion disturbed node guard heartbeat error if node guarding heartbeat is activated no synch objects if synch monitoring is activated IN yellow ON binary output switched 2 0 Hz diagnosis failure OUT yell...

Page 15: ...rred to PWM value 1000 Channel 2 4 6 8 pin 2 Semiconductor outputs with diagnostic capability wire break and short circuit can be configured as short circuit and overload protected Switching voltage 1...

Page 16: ...technical alterations without prior notice CR2032 page 4 PWM PWM PWM PWM Abbreviations CANH CAN interface high CANL CAN interface low GNDO ground output GNDS ground module PWM output for pulse width m...

Page 17: ...1 chan 1 o 4 2 o Bit 4 CR2032 Assignment of the LEDs to the connections 10 Fault correction 10 1 EMCY Object The following error codes to DSP 401 and DSP 301 are supported EMCY Code Error Reg Addition...

Page 18: ...channel 4 pin 4 wire break 0b 0000 0100 channel 6 pin 4 wire break 0b 0000 1000 channel 8 pin 4 wire break 0b 0001 0000 channel 2 pin 2 wire break 0b 0010 0000 channel 4 pin 2 wire break 0b 0100 0000...

Page 19: ...0x03 0 OFF 3 voltage 0 10 000 mV 6 ratiometric 0 1000 7 current 0 20 000 A 9 voltage 0 32 000 mV A binary input with analogue evaluation B binary input with analogue evaluation with diagnosis 2000 0A...

Page 20: ...used to access the mod ule in the CANopen network 20F2 20F3 0 Setting of the Baud rate u8 rw 0x04 Baud rate of the CAN network 0 1000 kBaud 1 800 kBaud 2 500 kBaud 3 250 kBaud 4 125 kBaud default 5 10...

Page 21: ...the synch message 1006 0 Communic Cycle u32 rw 0x00000000 Max time between 2 synch objects in s Useful resolution 1ms 1008 0 Device name str ro CR2032 Device name 1009 0 HW Version str ro x x Hardware...

Page 22: ...tttt node number If nn or tttt 0 no monitoring is carried out Note Node monitoring with node guarding or heartbeat is only to be used as an alternative 1017 0 Producer heartbeat time u16 rw 0x00 Time...

Page 23: ...2 0b 1000 0000 channel 8 pin 2 1601 0 Mapping Rec PDO 2 u32 ro 0x04 Number of the application objects linked with the analogue output PDO 1601 1 Index in the object directory u32 ro 0x6411 01 6411 Sld...

Page 24: ...0x00 synch acyclic 0x01 0xF0 synch cyclic Analogue values are only transferred after n synch objects n 0x01 1 0xF0 240 0xFC 0xFD not implemented 0xFE asynch man spec event Analogue values are immedia...

Page 25: ...cuit to ground 1A00 4 Index in the object directory u32 ro 0x2020 04 Idx 2020 Sldx 04 contains the binary value channel 7 pin 4 00 00 00 00 00 00 01 00 with diagnosis 00 00 00 00 00 00 FE FF short cir...

Page 26: ...0 1000 current 0 20 000 A voltage 0 32 000 mV binary input with analogue evaluation 01 00 00 00 00 00 00 00 binary input with analogue evaluation with diagnosis 00 00 00 00 FE FF 00 00 short circuit...

Page 27: ...CAN based network protocol on application level with an open configuration interface object directory CiA CAN in Automation e V user and manufacturer organisation in Germany Erlangen Definition and co...

Page 28: ...e network participants by a higher master node as well as the monitoring of this polling process by the slave participants Node ID node identifier identification of a participant in the CANopen networ...

Page 29: ...ubindex within the object directory of a CANopen device Start Guarding start node guarding str data type string variable for strings such as text load Sync Error missing Sync OBJ in the adjustable com...

Reviews: