4 Installation
► Disconnect the system from power before installation�
► For installation choose a flat mounting surface�
The entire bottom of the module must lie flat on the mounting surface�
► Screw the lower part onto the mounting surface using M4 screws and
washers (1)� Tightening torque 1�8 Nm�
► Carefully place the yellow AS-i flat cable into the profile slot�
► Carefully place the black AS-i flat cable for external voltage supply into the
profile slot�
► Position the upper part and fix it using the supplied M3�5 screws (2)�
Tightening torque 1�2���1�4 Nm�
► Fix the module onto the mounting surface using M4 or M5 screws and
washers (4)� Tightening torque max� 1�8 Nm�
Use stainless steel sleeve (E70402)* for installation in case of high mechanical
stress�
► Connect the plugs of the sensors (5) to the M12 sockets�
Tightening torque 0�8���1�5 Nm�
► Cover the unused sockets with protective caps (E73004)*�
Tightening torque 0�6���0�8 Nm�
► The flat cable end seal (E70413)* must be used if the module is at the end of
the cable line�
*to be ordered separately
In case of interference coupling to the sensor cables or the black flat cable
(24 V DC auxiliary supply) the use of the functional earth springs can
improve the EMC�
Requirement:
an interference-free and low-resistance connection to the machine ground�
► If necessary, you can ground the module via the functional earth
springs (5)�