AL4142
Remote I/O module 16 DI
34
u
Click on
to save the changes to the device.
w
The arrangement of the digital input channels is configured.
9.2.3.3 Configuring input filters
u
Observe the notes on input filters:
Available parameters:
Name
Description
Value range
Access
[pin2] > [debounce_time]
Pin 2: debounce time (= value * 0.1 milisec-
onds)
• 0: 0 ms (default)
…
• 500: 50 ms
rw
1
[pin2] > [hold_time]
Pin 2: Hold time (= value * 0.1 milliseconds)
• 0: 0 ms (default)
…
• 60000: 6000 ms
rw
1
[pin2] > [hold_level]
Pin 2: Hold level
• low: hold LOW
• high: hold HIGH (default)
rw
1
[pin2] > [invert]
Pin 2: Inversion
• signal not inverted: do not invert
(default)
• signal inverted: invert
rw
1
[pin4] > [debounce_time]
Pin 4: debounce time (= value * 0.1 milisec-
onds)
• 0: 0 ms (default)
…
• 500: 50 ms
rw
1
[pin4] > [hold_time]
Pin 4: Hold time (= value * 0.1 milliseconds)
• 0: 0 ms (default)
…
• 60000: 6000 ms
rw
1
[pin4] > [hold_level]
Pin 4: Hold level
• low: hold LOW
• high: hold HIGH (default)
rw
1
[pin4] > [invert]
Pin 4: Inversion
• signal not inverted: do not invert
(default)
• signal inverted: invert
rw
1
1
The parameter can only be changed if no connection to the fieldbus controller is active
Requirements:
ü
IoT Core Visualizer has been launched.
ü
The [Parameter] menu is active.
u
Select the [io] > [port[n]] submenu (n: 1...8).
w
The menu page shows the current settings.
u
Set the parameters.
u
Click on
to save the changes to the device.
w
The filters of the digital inputs are configured.
9.2.3.4 Configuring counter modules
u
Observe the notes on counter modules:
If the operating mode of a counter module is changed, the current counter values will be reset
and any active events will be deleted.