background image

Operating instructions

Ethernet switch

AL3050

11392988 / 00   04 / 2021

GB

Summary of Contents for AL3050

Page 1: ...Operating instructions Ethernet switch AL3050 11392988 00 04 2021 GB ...

Page 2: ...et ports 6 5 Installation 7 5 1 Install device 7 6 Electrical connection 8 6 1 Overview 8 6 2 General wiring information 8 6 2 1 Cabling 8 6 3 Ethernet 8 6 4 Ground connection 9 6 5 Voltage supply 9 7 Operating and display elements 10 7 1 LEDs 10 7 1 1 Voltage supply 10 7 1 2 Ethernet 10 8 Set up 11 9 Maintenance repair and disposal 12 9 1 Cleaning the housing surface 12 ...

Page 3: ...n the unit packaging or at www ifm com 1 1 Symbols used Requirement Instructions Reaction result Designation of keys buttons or indications Cross reference Important note Non compliance may result in malfunction or interference Information Supplementary note 1 2 Change history Version Subject Date 00 New creation of the document 04 2021 GB ...

Page 4: ...t of the system Read this document before setting up the product and keep it during the entire service life The product must be suitable for the corresponding applications and environmental conditions without any restrictions Only use the product for its intended purpose Ò Intended use If the operating instructions or the technical data are not adhered to personal injury and or damage to property ...

Page 5: ...nded use The device is used for networking of up to 6 Ethernet devices The device is designed for use in Ethernet networks The device is designed for use outside of a control cabinet The device is designed for the use in vehicles GB ...

Page 6: ...e name Reset device MAC address table Capacitance 2000 entries MAC Aging Time 200 400 s Quality of Service IEEE 802 1p IEEE 802 1Q Priority queues 4 4 2 Ethernet ports Supported transmission standards 10Base T IEEE 802 3i 100Base TX IEEE 802 3u Auto negotiation of the transmission rate Auto Negotiation Polarity detection and correction Auto Polarity Automatic detection of transmit and receive chan...

Page 7: ...ice u Disconnect the power of the machine before installation u Use a flat mounting surface for installation u Please observe the maximum tightening torque u Fasten the module onto the mounting surface using M5 screws and washers tightening torque 1 8 Nm GB ...

Page 8: ... of the device with basic insulation according to EN61010 1 6 2 1 Cabling The M12 connection parts in the device comply with the ingress resistance requirements of the standard EN 61076 2 101 To adhere to the protection rating only cables certified to this standard must be used The system architect undertakes to ensure the ingress resistance of cables they have cut to length u Carry out the fittin...

Page 9: ...ice is connected to the supply voltage US via the power IN port The supply voltage US supplies the device with voltage Max current consumption 100 mA 12 V 50 mA 24 V The port X31 has overvoltage protection US The port X31 has reverse polarity protection US The port X31 has an inrush current limitation max current 3 A ATTENTION Current surge with high voltage input due to disconnection of the devic...

Page 10: ...LNK ACT port X01 7 1 1 Voltage supply LED Description Colour State Description US Voltage supply status Green off no supply voltage is applied or the applied supply voltage is too low on Supply voltage applied 7 1 2 Ethernet LED Description Colour State Description LNK ACT Status Connection Activity Green off no Ethernet connection on Ethernet connection established flashes Data transmission ...

Page 11: ... up u Install the device correctly u Establish a correct electrical connection with the device w Once connected to the supply voltage the device will start w The LEDs show the status of the device w The unit is ready for operation GB ...

Page 12: ... way in accordance with the applicable national regulations when it is no longer used 9 1 Cleaning the housing surface Clean the surface of the device when necessary u Disconnect the device u Clean the device from dirt using a soft chemically untreated and dry cloth u In case of severe soiling use a damp cloth u Do not use any caustic cleaning agents for this ...

Reviews: