40
ifm
Device Manual IO-Link Master with Modbus interface CabinetLine 8 Ports IP 20 (AL1940)
05 / 2018
Configuration
IoT Core
>
8.2.9
Configure IO-Link devices
11002
The ifm IoT Core supports the configuration of the connected IO-Link devices. A parameter is
accessed via IO-Link index and subindex (
→ IO Device Description (IODD) of the device)
The user can use the following services:
Service
Description
Access
iolinkmaster/port[n]/iolinkdevice/iolreadacyclic
Acyclic reading of a parameter of an IO-Link device
r
iolinkmaster/port[n]/iolinkdevice/iolwriteacyclic
Acyclic writing of a parameter of an IO-Link device
rw
n ... 1...8
r = read only
rw ... read and write
>
8.2.10
Control IO-Link master
17963
The device can be controlled via the following services:
Service
Description
Access
firmware/version
Firmware version of the IO-Link master
r
firmware/reboot
Reboot IO-Link master
rw
firmware/signal
Identify IO-Link master
rw
firmware/factoryreset
Reset IO-Link master to factory settings
rw
r ... read only
rw ... read and write