IO-Link Master with IoT Interface DataLine 8 Ports IP 65 / IP 66 / IP 67
64
>
13.1.4
Inputs
34069
Inputs
Number of digital inputs
16; (IO-Link Port Class A: 8 x 2)
Switching level high [V]
11...30
Switching level low [V]
0...5
Digital inputs protected against short circuits
yes
>
13.1.5
Outputs
34053
Outputs
Number of digital outputs
8; (IO-Link Port Class A: 8 x 1)
Max. current load per output [mA]
3
00
Short-circuit protection
yes
>
13.1.6
Interfaces
52260
Interfaces
Communication interface
Ethernet; IO-Link
Communication interface
IO-Link; TCP/IP; TCP/IP JSON
Ethernet
Transmission standard
10Base-T; 100Base-TX
Transmission rate [MBit/s]
10; 100
Protocol
DCP, DHCP, Auto IP
Factory settings
IP address: 169.254.X.X
Subnet mask: 255.255.0.0
Gateway IP address: 0.0.0.0
MAC address: see type label
IO-Link master
Type of transmission
COM 1 / COM 2 / COM 3
IO-Link revision
V1.1
Number of ports class A
8