IO-Link Master with Modbus TCP Interface DataLine 4 Ports IP 65 / IP 66 / IP 67
102
>
Error codes
34342
Error code
Description
0x71
Service not available (unknown command has been sent to the IO-Link port)
0x72
Port blocked (another cyclic process accesses the IO-Link port)
0x73
Forbidden (access rights don't allow command processing)
0x74
Invalid data (wrong parameter has been sent in the command)
0x76
Wrong port (wrong port number)
0x77
Wrong port function (wrong port function or wrong parameter has been sent to the device)
0x78
Invalid length (set length is > 0x20)
0x80
Error in the device application; observe additional code (
→
Additional Codes
(
→ S.
>
Additional Codes
54584
Code
Name
Description
0x00
APP_DEV
Device application error - no details
0x11
IDX_NOTAVAIL
Index not available
0x12
SUBIDX_NOTAVAIL
Subindex not available
0x20
SERV_NOTAVAIL
Service temporarily not available
0x21
SERV_NOTAVAIL_LOCCTRL
Service temporarily not available - local control
0x22
SERV_NOTAVAIL_DEVCTRL
Service temporarily not available - device control
0x23
IDX_NOT_WRITEABLE
Access denied
0x30
PAR_VALOUTOFRNG
Parameter value out of range
0x31
PAR_VALGTLIM
Parameter value above limit
0x32
PAR_VALLTLIM
Parameter value below limit
0x33
VAL_LENOVRRUN
Parameter length overrun
0x34
VAL_LENUNDRUN
Parameter length underrun
0x35
FUNC_NOTAVAIL
Function not available
0x36
FUNC_UNAVAILTEMP
Function temporarily not available
0x40
PAR_SETINVALID
Invalid parameter set
0x41
PAR_SETINCONSIST
Inconsistent parameter set
0x82
APP_DEVNOTRDY
Application not ready
Additional Codes are only available, if Error Code = 0x80 (
→
Error codes
(