Electrical connection
Connect the device
>
6.5
Connect the device
17542
► Disconnect power.
► Connect the device via M12 socket X31 to 24 V DC
(20...28 V SELV/PELV; according to EN61010-1, secondary circuit
with maximum 30 V DC derived from applied voltage up to 300 V of
overvoltage category II).
Tightening torque: 0.6...0.8 Nm
Maximum cable length: 25 m
► To connect the device, use M12 connectors with protection rating IP
65 / IP 66 / IP 67 / IP 69K or higher (
→
Accessories
(
When using cable length greater than 25 m keep in mind the voltage drop as well as the
required minimum voltage supply of 20 V!