IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
31
>
9.1.7
IO-Link ports: Configure operating mode
33694
The IO-Link ports X01...X04 of the device support the following operating modes:
Digital input (DI): binary input signal at pin 4 (C/Q) of the IO-Link port
Digital output (DO): binary output signal at pin 4 (C/Q) of the IO-Link port
IO-Link: IO-Link data transfer via pin 4 (C/Q) of the IO-Link port
The user can set the operating mode separately for each IO-Link port.
To set the operating mode of an IO-Link port:
►
Select [Port x] menu (x = 1...4).
>
The menu page shows the current settings.
►
Set the following parameters as required:
Name
Description
Possible values
[Mode]
Operating mode of the IO-Link port
[Disabled]
Port deactivated
[DI]
Operation as digital input
[DO]
Operation as digital output
[IO-Link]
Operation as IO-Link interface
[Cycle time actual]**
Current cycle time of the data transfer between
IO-Link master and IO-Link device on the port
(value in microseconds)
Parameter can only be read
[Cycle time preset]*
Cycle time of the data transfer between the IO-Link
master and the IO-Link device at the port (value in
microseconds)
0
The device automatically sets
the fastest possible cycle time.
1
...
132800
1 microsecond
...
132800 microseconds
[Bitrate]**
Current transmission rate of the data transfer
between the IO-Link master and the IO-Link device
on the port
Parameter can only be read
* ... Parameter only available if [Mode] = [IO-Link]
** ... Parameter only visible if the IO-Link device is connected to the IO-Link port.
►
Save changed values on the device.