IO-Link Master with EtherNet/IP Interface StandardLine 4 Ports IP 65 / IP 66 / IP 67
26
>
9.1.2
IoT: Configure access rights
34046
The access rights define which instance may read and / or write the parameter data, process data and
event/diagnostic messages.
In order to configure the access rights to the IO-Link master:
►
Select [IoT] menu.
>
The menu page shows the current settings.
►
Set the following parameters as required:
Name
Description
Possible values
[Access Rights]
The access rights to the
parameter data, process data
and the event/diagnostic
messages of the IO-Link master
as well as the connected IO-Link
devices
[EtherNet/IP + IoT]
EtherNet/IP and IoT Core have read
and write access rights to parameters
and process data
EtherNet/IP and <IoT Core> have read
access rights to events/alarms
[EtherNet/IP + IoT
(read-only)]
EtherNet/IP has read and write access
rights to parameters and process data
EtherNet/IP has read access rights to
events/alarms
IoT Core only has read access rights to
parameters, process data and
events/alarms
[IoT only]
IoT Core has read and write access
rights to parameters and process data
IoT has read access rights to
events/alarms
EtherNet/IP has no access rights
►
Save changed values on the device.
If the parameter [Access rights] is set to [EtherNet/IP + IoT] via IoT and EtherNet/IP projection,
then the parameter values set in the EtherNet/IP projection software apply.
If the parameter [Access rights] is set to [IoT only] via IoT, then set the parameter [Access
rights] to [Keep settings] in the EtherNet/IP projection software.
Changes of the parameter [Access Rights] are only effective after restarting the device
(
→
Firmware: Reboot the device
(