Operating Instructions IO-Link Master with Profinet interface StandardLine 4 Ports IP 65 / IP 67 (AL1100)
2017-08-18
Configuration
>
8.6
Profinet: Programmers' notes
12761
The programmer can access on the following data from the PLC application:
Read device information of the AL1100
Read diagnostics and alarms
Set parameters of the connected IO-Link devices
The following sections show the available options.
Further information about the functional/operational blocks:
→ Help function of the Profinet
projection software
>
8.6.1
Read and write I&M datasets
2261
Symbol / function
block
Meaning
Remarks
GET_IM_DATA / FB
Function block for reading the I&M datasets of
a device
GET_IM_DATA only supports the reading
of the I&M0 dataset
Input parameters:
IM_TYPE = 0
RDREC
Function block for acyclic reading of datasets
Input parameters:
I&M0: Index = 0xAFF0
I&M1: Index = 0xAFF1
I&M2: Index = 0xAFF2
I&M3: Index = 0xAFF3
WRREC
Function block for acyclic writing of datasets
Observe access rights on datasets!
Input parameters:
I&M1: Index = 0xAFF1
I&M2: Index = 0xAFF2
I&M3: Index = 0xAFF3