SmartPLC SafeLine with PROFIBUS slave interface
105
Import device configuration
42301
NOTICE!
The import of a wrong or faulty boot project can lead to a non-safe state of the plant.
>
Risk of undesired system behaviour
► Check all safety functions of the installation after the import of the device configuration.
42301
NOTICE!
During the import the control functions of the device are not available. During the import the
device reboots.
>
Risk of undesired system behaviour
► Do not import the device configuration during operation of the plant!
NOTICE!
An interruption of the import can lead to a faulty device configuration.
>
Risk of data loss
► Do not disconnect the device during the import.
► Do not remove the SD card from the device before the import is completed.
To avoid that a wrong device configuration is restored:
► Check before the import if the required device configuration is saved on the SD card
(identification of the saved device configuration:
→
Export device configuration
(
)).
► Save only the device configuration to be imported in the root directory of the SD card.
To transfer a stored device configuration to the device:
1 Reboot the device
►
Insert the SD card containing the stored device configuration into the SD card slot.
►
Disconnect and the device from the power supply and reconnect it to the power supply.
>
Device reboots.
2 Select menu page
►
>
►
Select [Configuration] tab.
3 Restore the device configuration
►
Activate the [Import configuration] button.
>
A warning appears.
►
Confirm prompt with [OK].
>
The device configuration is loaded and saved onto the device.
>