SmartPLC DataLine with Profinet device interface
103
6.4
Connect and address AS-i slaves
41575
To integrate AS-i slaves into an AS-i network that is controlled by one of the AS-i masters of the
device:
1 Connect and address the AS-i slave
►
Connect ONE AS-i slave to be addressed to the requested AS-i network (AS-i 1 or AS-i 2) as described in the
corresponding installation instructions.
►
Assign the desired address to the AS-i slave
(→
Quick setup: Address the AS-i slaves connected to AS-i Master 1
) or →
Quick setup: Address
the AS-i slaves connected to AS-i Master 2
►
Optional: Repeat step 1 to connect and address further AS-i slaves.
2 Project the AS-i network
►
Carry out a projection adaptation on the AS-i master with the newly addressed AS-i slaves
(→
Quick setup: Project AS-i networks
>
The AS-i master adds the detected slaves (LDS) to the list of the projected slaves (LPS).
>
The AS-i slaves have a valid address and are integrated in the AS-i network.
>
6.5
Set up Profinet
41414
Detailed information on the configuration of the PROFINET-network:
→ Operating instructions
of the PROFINET-master
To integrate the device into a PROFINET-network:
1 Set interface parameters
►
>
>
►
Set interface parameters (→
PROFINET interface
(→ S.
2 Integrate the device with a GSDML file into a PROFINET-project
►
Copy GSDML file of the device on PC/laptop with the PROFINET-configuration software (→
Download GSDML
file
►
Load the device with the GSDML file into the device library of the PROFINET-configuration software (→ operating
instructions of the PROFINET-configuration software).
►
Integrate the device into the PROFINET-project.
3 Set device parameters, fieldbus modules and system behaviour
►
Set the following parameters in the PROFINET-configuration software:
– Device-specific parameters (→
Parameter data
(→ S.
– PROFINET-Modules (→
PROFINET modules
►
Set the system behaviour in the PROFINET-configuration software (e.g. watchdog)
4 Configuration activate
►
Store configuration and load to the PROFINETController (download).
►
PROFINET-Start controller.
>
The device is integrated into the PROFINET-network (→ status LED of the PROFINET-interface)
5 Select
►
>
>
►
Select the [Profinet data] tab.
>
Page shows the stored configuration.
>