42
11.3 Error indications
Warning message
[SC1]
Short circuit in OUT1�
LED8 for OUT1 flashes (→ 7 Operating and display elements).
[SC2]
Short circuit in OUT2�
LED7 for OUT2 flashes (→ 7 Operating and display elements).
[SC]
Short circuit in both outputs�
LED7 and LED8 flash (→ 7 Operating and display elements).
[OL]
Detection zone of volumetric flow or temperature exceeded�
[UL]
Below the detection zone of volumetric flow or temperature�
[Err]
•
Unit faulty / malfunction�
•
Measured value outside the detection zone�
[C�Loc]
Setting pushbuttons locked, parameter change rejected�
Active IO-Link communication�
[S�Loc]
Setting pushbuttons locked, parameter change rejected�
Unlock using parameter setting software�
[SEnS]
Sensor signal invalid�
•
Measuring pipe not sufficiently filled�
•
Medium with too low a conductivity�
[IOE�n]
Malfunctioning� The unit is faulty and must be replaced�
12 Technical data
Technical data and scale drawing at www.ifm.com → Data sheet search → Enter
the article number�