38
11.2.3 Set to the medium
► Select [MEdI] and set:
[HIGH] = For water and water-based media
Operating mode is optimised for suppression of deposits on the
probe.
[MId] =
For water-based media and media with a medium dielectric
constant value, e.g. oil-in-water emulsions.
Operating mode optimised for the detection of media with
increased foam build-up.
[LOW] = For oils and oil-based media
Note: Option only visible if [Prob] = [COAx].
►
Press [Enter].
►
Check proper function by an application test.
Then the unit changes to the operating mode.
If required (e.g. when mounted in a connection piece), carry out a tank adjustment
(parameter [tREF]) and set parameters to adapt to the application.
Setting ranges of all parameters: (→ 13.1)
Factory settings of all parameters: (→ 15)
11.2.4 Carry out tank adjustment
Menu item only visible if [LEnG] ≥ 260 mm and [Prob] = [rod].
►
.
►
Select [tREF].
►
Press [Enter].
> [nonE] or the value saved from the last tank adjustment (distance value)
is displayed.
►
Press [
▲
] or [
▼
] for at least 1 s.
>
The distance value is displayed (default value: 10 mm).
► Correct the value, if necessary, with [▲] oder [
▼
]. Incrementally by
pressing the button once or continuously by keeping the button pressed.
►
Press [Enter].
> [donE] is displayed.
►
Press [Enter] again.
> The unit reboots and then returns to the operating mode.