10.4.2 Set the standard unit of measurement for temperature
►
Select [Uni�T] and set the unit of measurement: [°C] or [°F]�
10.4.3 Configuration of the standard display
►
Select [SELd] and determine the standard measuring unit:
-[FLOW] = the current volumetric flow value in the standard unit of
measurement is displayed�
-[TEMP] = the current medium temperature is displayed in the standard
unit of measurement�
►
Select [diS] and set the update rate and orientation of the display:
-[d1] = update of the measured values every 500 ms�
-[d2] = update of the measured values every 1000 ms�
-[d3] = update of the measured values every 2000 ms�
-[rd1], [rd2], [rd3] = display as for d1, d2, d3; rotated by 180°�
-[OFF ] = the display is switched off in the operating mode�
10.4.4 Calibrate the curve of measured values for volumetric flow
►
Select [CGA] and set a percentage between 60 and 140 (100 = factory
setting)�
10.4.5 Reset calibration data
►
Select [CAr]�
►
Press and hold [Set] until [----] is displayed�
►
Briefly press [Mode/Enter]�
> The values are reset to the factory setting (CGA = 100)�
10.4.6 Set the measured value damping for volumetric flow
►
Select [dAP] and set the damping constant in seconds (t value 63 %)�
10.4.7 Set output status in fault condition
►
Select [FOU1] and set the value:
-[On] = The analogue signal goes to the upper end stop value�
-[OFF] = The analogue signal goes to the lower end stop value�
►
Select [FOU2] and set the value:
-[On] = The analogue signal goes to the upper end stop value�
-[OFF] = The analogue signal goes to the lower end stop value�