SmartController (CR2500) V05
Configurations
Set up programming system
4.1
Set up programming system
4.1.1
Set up programming system manually
Setup the target
When creating a new project in CoDeSys
®
the target file corresponding to the controller must be
loaded. It is selected in the dialogue window for all hardware and acts as an interface to the hardware
for the programming system.
Figure: Target system settings
At the same time, all important libraries and the PLC configuration are loaded when selecting the
target. These can be removed by the programmer or complemented by further libraries, if necessary.
NOTE:
The software versions suitable for the selected target must always be used:
•
of the operating system (
CRnnnn_Vxxyyyzz.H86
),
•
of the PLC configuration (
CRnnnn_Vxx.CFG
),
•
of the device library (
CRnnnn_Vxxyyyzz.LIB
),
•
and the further files (
→
chapter Overview of the files and libraries used,
→
page
CRnnnn device
article
number
Vxx: 00...99
target version number
yy: 00...99
release number
zz: 00...99
patch number
The basic file name (e.g. "
CR0032
") and the software version number "xx" (e.g. "
02
") must always have
the same value! Otherwise the controller goes to the STOP mode.
The values for "yy" (release number) and "zz" (patch number) do
not
have to match.
Also note: the following files must also be loaded:
•
The for the project required internal libraries (designed in IEC1131),
•
the configuration files (
*.CFG
)
•
and the target files (
*.TRG
).