IO-Link master
46
The following steps must be carried out to set the station address:
►
Click [Target System, PROFIBUS, Assign PROFIBUS Address] in [HW Config�]�
> The [Assign PROFIBUS Address] dialogue box opens�
►
If no Profibus address has been assigned yet, set bus address 126 under
[Current PROFIBUS Address]�
►
Set the desired bus address under [New PROFIBUS Address]�
►
Click [Apply] to assign the address�
►
Exit the dialogue box by clicking [OK]�
Access with the programming device (PG) to Profibus must be ensured for this� Otherwise the follow-
ing error occurs:
Right now you have not made any Profibus interface parameter setting to the access point [S7
ONLINE]�
►
Call up [Set PG/PC Interface] to assign the Profibus interface parameter setting�
26.6 Identification and maintenance
The identification and maintenance (I&M) data records are split over several STEP
7 dialogue boxes� An online connection to the device is required to display the I&M
data records�
The following steps must be carried out:
Switch the hardware manager to online view�
►
Right-click on the module, then select [Module Information]�
►
In the [General] tab, the order number / description, hardware version and
firmware version are listed in the [Version] area�