Command 0x10 – set mode
23461
The command changes the operating mode of an IO-Link port of the AL1121.
Corresponding parameter: [Port Mode] (
→
Port configuration
(
>
Command request
22990
Byte
Bit 7
Bit 6
Bit 5
Bit 4
Bit 3
Bit 2
Bit 1
Bit 0
4
Port no. (LSB)
5
Port no. (MSB)
6
reserved
7
reserved
8
reserved
9
reserved
10
Trigger
0x10
11
Target mode
12...45
reserved
Legend:
Port no. (LSB)
Number of the IO-Link port (low
byte)
Port no. = 0xXX
YY
Port no. (LSB) = 0x
YY
8 bits
0x01 = port X01
0x02 = port X02
...
0x04 = port X04
Port no. (MSB)
Number of the IO-Link port (high
byte)
Port no. = 0x
XX
YY
Port no. (MSB) = 0x
XX
8 bits
0x00
Trigger
Control of the command
execution
1 bit
0x0 = do not process command
0x1 = execute command
Target mode
Operating type of the IO-Link port 8 bits
0x00 = deactivated
0x01 = operation as digital input (DI)
0x02 = operation as digital output (DO)
0x03 = operation as IO-Link intervals