SmartPLC SafeLine AC4S with fieldbus interfaces
103
>
9.1.2
Load safe application to AC4S
43105
In the event of simultaneous use of network variables and safety network variables:
→
Note:
Projects with network variables
(
On first log-in to the fail-safe controller the programmer is asked to enter an instance
identification. The instance identification is the serial number of the device without the leading
zeros.
Example:
Serial number:
000000569158
Instance identification:
569158
To determine the serial number of the device:
→ Label underneath the Fieldbus interface (X6/X7) or
→ GUI/web interface:
►
>
To transfer the safe application of the CODESYS project to AC4S:
Requirements:
>
Communication path of the fail-safe PLC is correctly set (→
Configure programming interface
1 Load safe application to AC4S
►
In the safety extension area of the device tree:
Mark [SafetyApp] and activate with [Projekt] > [Aktive Applikation setzen].
►
Select [Online] > [Login].
>
CODESYS changes to the online mode.
>
CODESYS compiles the safe application and transfers it to the AC4S.
►
Observe the warnings and notes.
2 Start safe application
►
Start [SafetyApp].
>
[SafetyApp] is in the RUN state.
3 Optional: Teach code sequences
►
Teach code sequences of the safe AS-i input slaves (→
Process safety time for the AC4S
4 Optional: Create safe boot application
►
Pin safe application (→ CODESYS online help).
►
Select [Online] > [Create boot application].
>
CODESYS stores the safe application non-volatilely on AC4S.
When the safe boot application has been created on the AC4S, the fail-safe PLC remains in
the "Debug operation" operating status.
► Note remarks about changing the operating states (→
Change between the states
(
>