Interrupt Input
When a quick response to an external input is required, such as positioning control, the interrupt input can call a subroutine to
execute an interrupt program.
Six inputs I0, I1, I3, I4, I6, and I7 can be designated to execute interrupt at a rising and/or falling edge of input pulses. When an
interrupt is initiated by inputs I0, I1, I3, I4, I6 and I7, program execution immediately jumps to a predetermined label number
stored in special data registers D8215, D8032 through D8035, and D8214 respectively. The
Function Area Settings
dialog box is
used to designate inputs I0, I1, I3, I4, I6 and I7 as an interrupt input, normal input, high-speed counter input, or catch input.
Normal input signals to input terminals are read when the END instruction is executed at the end of a scan.
Since these settings relate to the user program, the user program must be downloaded to the FC6A Series MicroSmart after
changing any of these settings.
Interrupt Input Terminals, Special Data Registers, and Special Internal Relays for Interrupt Inputs
Programming WindLDR
1.
From the WindLDR menu bar, select
Configuration
>
Input Configuration
.
The
Function Area Settings
dialog box for Input Configuration appears.
2.
Select
Interrupt Input
in the Groups 1 through 6 pull-down list boxes. the Interrupt Input dialog box appears.
3.
Select an interrupt edge in the pull-down list for each group.
Disable and Enable Interrupts
The interrupt inputs I0, I1, I3, I4, I6, and I7 and timer interrupt are normally enabled while the FC6A Series MicroSmart is running,
and can also be individually disabled using the DI instruction or enabled using the EI instruction. When interrupt inputs I0, I1, I3,
I4, I6, and I7 are enabled, special internal relay M8137 through M8143, and M8167 are turned on, respectively. See Chapter 14
"Refresh Instructions" in the "FC6A Series MicroSmart LAD Programming Manual".
Group
Interrupt Input No.
Interrupt Input Jump Destination Label No.
Interrupt Input Status
Group 1
I0
D8215
M8137
Group 2
I1
D8032
M8140
Group 3
I3
D8033
M8141
Group 4
I4
D8034
M8142
Group 5
I6
D8035
M8143
Group 6
I7
D8214
M8167
Interrupt Input Rising/
Falling Edge Selection
Interrupt at Rising Edge
Interrupt occurs when the
interrupt input turns on.
Interrupt at Falling Edge
Interrupt occurs when the
interrupt input turns off.
Interrupt at Both Edges
Interrupt occurs when the
interrupt input turns on or off.
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...