5: F
UNCTIONS
AND
S
ETTINGS
5-24
FC6A S
ERIES
M
ICRO
S
MART
A
LL
-
IN
-O
NE
T
YPE
U
SER
’
S
M
ANUAL
FC9Y-B1722
■
Overflow
When the current value exceeds 4,294,967,295, the special internal relay turns on for only one scan. When the current value
overflows, it becomes 0.
■
Underflow
When the current value falls below 0, the special internal relay turns on for only one scan. When the current value underflows, it
becomes 4,294,967,295.
■
Comparison output reset
When the special internal relay turns on, the comparison output selected on
High-speed Counter Settings
turns off.
■
Reset input
When reset input is turned on, the current value returns to the reset value.
■
Preset value, reset value storage locations
The preset value and the reset value for the high-speed counter are stored in special data registers as 2 words.
In the WindLDR
Function Area Settings
, when
32-bit Data Storage Setting
is set to
From Lower Word
, the lower word
is stored in the first device.
■
HSC reset input and reset status
When the HSC reset input is enabled in group 1 or group 5, turn on HSC reset input I2 or I5 to return the current value to the
reset value.
In this situation, reset status turns on for only one scan.
To use the reset input with the group 1 or group 5 single-phase high-speed counter, use I2 or I5. When not using I2 or I5 as an
external clear input, they can be used as normal input.
■
Count direction flag
These special internal relays maintain whether the Group 1 or Group 5 current value is being added or subtracted.
When these special internal relays are on, they indicate addition. When they are off, they indicate subtraction.
Group
1
2
3
4
5
6
Read/Write
Overflow
M8161
M8055
M8165
M8166
M8163
M8063
R
Group
1
2
3
4
5
6
Read/Write
Underflow
M8162
—
—
—
M8164
—
R
Group
1
2
3
4
5
6
Read/Write
Comparison Output Reset
M8030
M8051
M8034
M8040
M8044
M8057
R/W
Group
1
2
3
4
5
6
Read/Write
Reset Input
M8032
M8053
M8036
M8042
M8046
M8061
R/W
Group
1
2
3
4
5
6
Read/Write
Preset Value (Upper word)
D8212
D8194
D8220
D8224
D8228
D8200
R
Preset Value (Lower word)
D8213
D8195
D8221
D8225
D8229
D8201
Reset Value (Upper word)
D8216
D8196
D8234
D8236
D8232
D8202
R/W
Reset Value (Lower word)
D8217
D8197
D8235
D8237
D8233
D8203
Group
1
2
3
4
5
6
Read/Write
HSC Reset Input
I2
—
—
—
I5
—
—
Reset Status
M8130
—
—
—
M8135
—
R
Group
1
2
3
4
5
6
Read/Write
Count Direction flag
M8027
—
—
—
M8043
—
—
Reset input
N
N-1
N+1
Reset value (initial value)
Current value
HSC reset input
Reset status
N
N-1
N+1
Reset value (initial value)
Current value
One scan
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...