The high-speed counter as the following five counting modes.
■
Adding counter (single-phase high-speed counter)
The adding counter counts up with the rise in pulse input.
■
Up/down selection reversible counter (single-phase high-speed counter)
Up/down selection reversible counter can switch between addition and subtraction by pulse input with the up/down selection
input. When the up/down selection input is on, the counter counts up with the rise in pulse input. When the up/down selection
input is off, the counter counts down with the rise in pulse input.
■
Dual-pulse reversible counter (single-phase high-speed counter)
This counter switches between the up count and the down count with pulse input (up) and pulse input (down). When a pulse is
input to pulse input (up), the counter counts up with the rise in pulse input. When a pulse is input to pulse input (down), the
counter counts down with the rise in pulse input.
■
2-edge count (two-phase high-speed counter)
This counter counts by the phase difference between the A-phase and B-phase pulse input. When the A-phase precedes the B-
phase, the counter counts up with the rise and fall of the B-phase. When the B-phase precedes the A-phase, the counter counts
down with the rise and fall of the B-phase.
■
4-edge count (two-phase high-speed counter)
This counter counts by the phase difference between the A-phase and B-phase pulse input. When the A-phase precedes the B-
phase, the counter counts up with the rise and fall of the A-phase and the B-phase. When the B-phase precedes the A-phase,
the counter counts down with the rise and fall of the A-phase and the B-phase.
10
11
12
13
14
Current value
Pulse input
(I0, I1, I3, I4, I6, I7)
10
11
12
11
10
Current value
Up/down selection
input
(I1, I7)
Pulse input
(I0, I6)
10
11
12
11
10
Current value
Pulse input (down)
Input
(I1, I7)
Pulse input (up)
(I0, I6)
0
1
1
0
2
2
3
3
4
B-phase
Current
value
A-phase
0
1
2
3
4
5
6
7
7
6
5
4
3
2
1
0
8
Current
value
B-phase
A-phase
Summary of Contents for FC6A series
Page 1: ...B 1722 2 FC6A SERIES All in One Type User s Manual ...
Page 10: ...TABLE OF CONTENTS Preface 9 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 28: ...1 GENERAL INFORMATION 1 18 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 286: ...6 DEVICES 6 32 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 334: ...7 HMI FUNCTION 7 48 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 340: ...8 INSTRUCTIONS REFERENCE 8 6 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 360: ...9 FUNCTIONAL MODULES 9 20 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...
Page 368: ...10 ANALOG CARTRIDGE 10 8 FC6A SERIES MICROSMART ALL IN ONE TYPE USER S MANUAL FC9Y B1722 ...