4: A
NALOG
I/O C
ONTROL
4-14
END Refresh Type
The operating status of each analog input channel is stored to a data register, such as D761 or D767, allocated to analog
input channel 1 or 2 on analog module number 1 through 7 depending on the mounting position.
The analog input operating status data is updated whether the CPU module is running or stopped. When the CPU module
is running, the update occurs at the END processing of every scan or 10 ms, whichever is longer. When the CPU module is
stopped, the update occurs every 10 ms.
Ladder Refresh Type
The operating status of each analog input channel is stored to a data register determined by the data register number
selected in the Configure Parameters dialog box of the ANST macro.
Status Code
Analog Input Operating Status (END refresh type)
0
Normal operation
1
Conver ting data (during the first data conversion after power-up)
2
Initializing
3
Invalid parameter or analog input channel not available on the installed analog module
4
Hardware failure (external power supply failure)
5
Incorrect wiring (input data over valid range)
6
Incorrect wiring (input data below valid range or current loop open)
Operating Status Bit
Analog Input Operating Status (Ladder refresh type)
Bit 0
0
Operating status bit
Normal operation
1
Initializing, changing configuration, hardware initialization error
Bit 1
0
Parameter bit
Parameter configuration normal
1
Parameter configuration error
Bit 2
0
External power supply bit
External power supply normal
1
External power supply error
Bit 3
0
Maximum value over bit
Within the maximum value
1
Maximum value over error
Bit 4
0
Minimum value over bit
Within the minimum value
1
Minimum value under error
Bit 5 to Bit 15
0
Reser ved
Normal operation