Indirect Read and Indirect Write Settings
The indirect specification of a device address means to add a value (indirect value) to the address number of the set
device address and use that address number as the actual read source or write destination. You can change the read
source or write destination address number just by changing this indirect value.
Indirect read
Add the indirect value to the address number of the device address set as the read source and read the value of the
indirectly specified device address.
Example: To read an indirectly specified value of device address into LDR200
When the device set as the read source is LDR10 and the indirect value’s device address is D21, if 4
(indirect value: 4) is set in D21, the device address of the value actually read is LDR14.
Indirect write
Add the indirect value to the address number of the device address set as the write destination and write a value to
the indirectly specified device address.
Example: To write the value in LDR20 to an indirectly specified device address
When the device set as the write destination is LDR100 and the indirect value’s device address is D20, if 3
(indirect value: 3) is set in D20, the device address of the value actually written is LDR103.
Parts you can indirectly read and indirectly write
Device address set as read source
Device address with actually read value
Device address for Indirect value
200
LDR11
300
LDR12
100
LDR10
500
LDR14
4
D21
500
LDR200
4 words
Indirect value
Read
LDR13
400
200
LDR101
300
LDR102
100
LDR100
1000
LDR103
3
D20
1000
LDR20
3 words
Indirect value
Device address set as write source
Device address with actually written value
Device address for Indirect value
Write
Part
Indirect read
Indirect write
Word Button
YES
YES
Multi-Button
YES
YES
Numerical Input
YES
YES
Character Input
YES
YES
Numerical Display
YES
NO
Word Write Command
YES
YES
Script Command
YES
YES
Multi-Command
YES
YES
• Enter the value for indirect values as the data type UBIN16(W). Indirect values can be set in the range of
0 to 32767. When an indirect write is executed with an out-of-range indirect value, “Device range error”
is displayed. Similarly, when an indirect read is executed, the previous value before the indirect value
changed is retained for a data display part, and “Device range error” is displayed for a part that is not a
data display part.
• For reading device address indirectly, decide the read source address number after the indirect value changes
and after the screen changes, and then read the value of device address. For the device address of an
external device, communication may take some time as the value is read from the external device, so when
transferring or calculating the data that was read, repeatedly execute the corresponding part.
Summary of Contents for WindO/I-NV4
Page 1: ...B 1701 16 User s Manual...
Page 108: ...5 WindO I NV4 Common Operations and Settings 2 76 WindO I NV4 User s Manual...
Page 256: ...7 BACnet Communication 3 148 WindO I NV4 User s Manual...
Page 372: ...6 Screen Restrictions 5 32 WindO I NV4 User s Manual...
Page 390: ...5 Part Library Function 6 18 WindO I NV4 User s Manual...
Page 420: ...3 Text 7 30 WindO I NV4 User s Manual...
Page 628: ...2 Multi State Lamp 9 34 WindO I NV4 User s Manual...
Page 924: ...4 Meter 11 76 WindO I NV4 User s Manual...
Page 990: ...7 Timer 12 66 WindO I NV4 User s Manual...
Page 1030: ...4 Using Data and Detected Alarms 13 40 WindO I NV4 User s Manual...
Page 1098: ...4 Using the Data 15 22 WindO I NV4 User s Manual...
Page 1248: ...5 Restrictions 22 18 WindO I NV4 User s Manual...
Page 1370: ...2 Monitoring on the MICRO I 25 28 WindO I NV4 User s Manual...
Page 1388: ...4 Restrictions 26 18 WindO I NV4 User s Manual...
Page 1546: ...5 Module Configuration Dialog Box 30 36 WindO I NV4 User s Manual...
Page 1614: ...3 Settings 34 14 WindO I NV4 User s Manual...
Page 1726: ...5 Text Alignment A 10 WindO I NV4 User s Manual...