
IDEC SmartRelay functions
IDEC SmartRelay Manual
122
4.3.1
Designation of the inputs
Logical inputs
Here, you will find the description of the connectors you can
use to create a logical link to other blocks or to the inputs of
the IDEC SmartRelay unit.
•
S (Set):
A signal at input S sets the output to logical “1”.
•
R (Reset):
The reset input R takes priority over all other inputs and
resets the outputs.
•
Trg (Trigger):
This input is used to trigger the start of a function.
•
Cnt (Count):
This input is used for counting pulses.
•
Fre (Frequency):
Frequency signals to be evaluated are applied to this input.
•
Dir (Direction):
This input determines the direction of count, for example.
•
En (Enable):
This input enables a block function. When this input is “0”,
other signal to the block will be ignored.
•
Inv (Invert):
A signal at this input inverts the output signal of the block.
•
Ral (Reset all):
All internal values are reset.
Connector X at SF inputs
SF inputs connected to connector x are set low. That is, the
inputs carry a ‘lo’ signal.
Parameter inputs
At some of the inputs you do not apply any signals. You con-
figure the relevant block values instead. Examples:
•
Par (Parameter):
This input will not be connected. Here, you set the rele-
vant block parameters (times, on/off thresholds etc.).
•
No (Cam):
This input will not be connected. Here, you configure the
time patterns.
•
P (Priority):
This is an open input. Here, you define priorities and spec-
ify whether a message is to be acknowledged in RUN.
Courtesy of Steven Engineering, Inc. ● 230 Ryan Way, South San Francisco, CA 94080-6370 ● General Inquiries: (800) 670-4183 ● www.stevenengineering.com