On-/Off-times
Any time between 00:00 h and 23:59 h is possible.
– : – means: No on-/off-times set.
Setting the Seven-day time switch
To set the on-/off-times:
1. Move the cursor to one of the Cam parameters of the
timer (e.g. No1).
2. Press
OK
. IDEC SmartRelay opens the Cam parameter
assignment screen form. The cursor is positioned on the
weekday.
3. Press
▲
and
▼
to select one or several weekdays.
4. Press to move the cursor to the first position of the
on-time.
5. Set the on-time.
Modify the value at the respective position, using the
keys
▲
and
▼
. Move to the cursor to the various posi-
tions, using the keys and . At the first position, you
can only select the value – : –
(– : – means: No on-/off-times set).
6. Press to move the cursor to the first position of the
off-time.
7. Set the off-time (in same way as in step 5).
8. Confirm your entries with
OK
.
The cursor is now positioned on the No2 parameter
(Cam2) and you can configure a further cam.
Note
For information on timer accuracy, refer to the technical data and to
Chapter 4.3.2.
▲
▲
▲
▲