IDEC SmartRelay Manual
3.6.10 Correcting programming errors
Programming errors can be corrected easily in IDEC
SmartRelay :
• Provided editing mode is not yet closed, you can revert by
one step by pressing
ESC
.
• If you have already configured all inputs, simply reconfig-
ure the faulty input:
1. Move the cursor to the faulty position
2. Change to editing mode. Press
OK
3. Enter the correct input circuit.
You can only replace a block with a block that has exactly the
same number of inputs. However, you can delete the old
block and then insert a new one. You can choose any new
block.
3.6.11 Selecting analog output values for RUN/STOP
transition
You can select the analog values that are output at the two
analog outputs when IDEC SmartRelay changes from RUN
mode to STOP mode
.
In the programming menu:
1. Move the “>” cursor to ‘
Edit..
’:
Press
▼
or
▲
2. To accept ‘Edit..’:
Press
OK
3. Move the “>” cursor to ‘
AQ in Stop
’: Press
▼
or
▲
4. To accept ‘AQ in Stop’:
Press
OK
IDEC SmartRelay shows the following display:
>Defined
Last
AQ in Stop
Last
The current setting for the analog output channels is shown
on the bottom row. The default setting is ‘Last’.
You can select either ‘Last’ value (i.e. analog output values
are held at their last value) or ‘Defined’ value (i.e. analog
output values are set to specific values). When IDEC
SmartRelay changes from RUN mode to STOP mode, the