2 Analog Cartridge
29-30
SmartAXIS Touch User's Manual
2.4 Specifications
■
Analog Output Specifications
■
Analog Input Specifications
Type Number
FC6A-PK2AV
FC6A-PK2AW
FC6A-PJ2A
FC6A-PJ2CP
Rated Voltage
5.0 V, 3.3 V (Supplied from the Touch)
Consumption Current
5.0 V: 70 mA
3.3 V: 30 mA
5.0 V: 185 mA
3.3 V: 30 mA
5.0 V: -
3.3 V: 30 mA
5.0 V: -
3.3 V: 30 mA
Weight
15 g
15 g
15 g
15 g
Type Number
FC6A-PK2AV
FC6A-PK2AW
Output Type
Voltage Range
0 to 10 V
-
Current Range
-
4 to 20 mA
Load
Impedance
2 k
Ω
min.
500
Ω
max.
Load Type
Resistance load
D/A
Conversion
Cycle Time
20 ms
20 ms
Settling Time
40 ms max.
20 ms max.
Total Output System Transfer Time 60 ms+1 scan
40 ms+1 scan
Output Error
Maximum Error at 25°C
±0.3% of FS
±0.3% of FS
Temperature Coefficient
±0.02%/°C of FS
±0.02%/°C of FS
Reproducibility After Stabilization Time
±0.4% of FS
±0.4% of FS
Non-linearity
±0.01% of FS
±0.01% of FS
Output Ripple
30 mV max.
30 mV max.
Overshoot
0%
0%
Maximum Error
±1.0% of FS
±1.0% of FS
Data
Digital Resolution
4,096 increments (12bit)
4,096 increments (12bit)
LSB Output Value
2.44 mV (0 to 10 V)
3.91 µA (4 to 20 mA)
Data Format in Application
0···4095 (0 to 10 V)
0···4095 (4 to 20 mA)
Monotonicity
Yes
Yes
Open Current Loop
-
Cannot be detected
Noise
Resistance
Maximum Temporary Deviation
during Electrical Noise Tests
±4.0% of FS max.
±4.0% of FS max.
Recommended Cable
Shielded twisted pair
Crosstalk
1 LSB max.
1 LSB max.
Isolation
None
None
Effect When Output is Incorrectly Wired
No Damage
No Damage
Calibration to Maintain Rated Accuracy
Not possible
Not possible
Type Number
FC6A-PJ2A
FC6A-PJ2CP
Input Type
Voltage
input
Current
input
Resistance thermometer
Thermocouple
Input Range
0 to 10 V
4 to
20 mA
0 to
20 mA
Pt100:
-200 to +850 °C (-328 to 1562 'F)
Pt1000:
-200 to +600 °C (-328 to 1112 'F)
Ni100:
-60 to +180 °C (-76 to 356 'F)
Ni1000:
-60 to +180 °C (-76 to 356 'F)
(K)-200 to 1300 °C (-328 to 2372 °F)
(J)-200 to 1000 °C (-328 to 1832 °F)
(R)0 to 1760 °C (32 to 3200 °F)
(S)0 to 1760 °C (32 to 3200 °F)
(B)0 to 1820 °C (32 to 3308 °F)
(E)-200 to 800 °C (-328 to 1472 °F)
(T)-200 to 400 °C (-328 to 752 °F)
(N)-200 to 1300 °C (-328 to 2372 °F)
(C)0 to 2315 °C (32 to 4199 °F)
Input Impedance
1 M
Ω
min. 250
Ω
max. 1 M
Ω
min.
Allowable Conductor Resistance
-
-
10
Ω
max.
-
Input Detection Current
-
-
TYP: 0.2 mA 1.0 mA max.
-
Summary of Contents for SmartAXIS Touch FT1A Series
Page 1: ...FT1A Series FT9Y B1390 4 SmartAXIS Touch User s Manual ...
Page 22: ...Contents Preface 21 SmartAXIS Touch User s Manual ...
Page 240: ...6 Using Library Screens 4 36 SmartAXIS Touch User s Manual ...
Page 416: ...2 Multi State Lamps 8 26 SmartAXIS Touch User s Manual ...
Page 558: ...9 Calendar 9 142 SmartAXIS Touch User s Manual ...
Page 668: ...6 Timer 11 52 SmartAXIS Touch User s Manual ...
Page 754: ...4 Using Data and Detected Alarms 13 34 SmartAXIS Touch User s Manual ...
Page 792: ...4 Using the Data 14 38 SmartAXIS Touch User s Manual ...
Page 810: ...4 Using the Data 15 18 SmartAXIS Touch User s Manual ...
Page 870: ...3 Text Manager 19 16 SmartAXIS Touch User s Manual ...
Page 924: ...6 Important Notes 20 54 SmartAXIS Touch User s Manual ...
Page 1036: ...5 User Communication 22 74 SmartAXIS Touch User s Manual ...
Page 1092: ...2 Monitoring on the Touch 24 26 SmartAXIS Touch User s Manual ...
Page 1142: ...2 Word Devices 27 18 SmartAXIS Touch User s Manual ...
Page 1186: ...2 Analog Cartridge 29 34 SmartAXIS Touch User s Manual ...
Page 1194: ...3 Handling Problems 30 8 SmartAXIS Touch User s Manual ...