13: S
CRIPTS
13-26
S
MART
AXIS P
RO
/ L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378
6. Bit Functions
Example 6.1
Set a bit
Script
Operation Description
Turns D0000.01 to 1. The result is the same as
[D0000.01] = 1
.
Example 6.2
Reset a bit
Script
Operation Description
Turns D0000.01 to 0. The result is the same as
[D0000.01] = 0
.
Example 6.3
Invert a bit
Script
Operation Description
Inverts 1 and 0 in D0000.01. The result is the same as
[D0000.01] = ~[D0000.01]
.
7. Word Functions
Arithmetic operations
Example 7.1
Maximum value
Script
Operation Description
Out of the values stored in D0100, D0110, D0120, D0130, and D0140, the maximum value is stored in D0200.
Up to 15 arguments can be used.
Example 7.2
Mininum value
Script
Operation Description
Out of the values stored in D0100, D0110, D0120, D0130, and D0140, the minimum value is stored in D0200.
Up to 15 arguments can be used.
Example 7.3
Exponential function
Script
Operation Description
Calculates the exponential function of the value of D0020 and the result is stored in D0010.
Only the data type F (float) can be used.
SET([D0000.01]);
RST([D0000.01]);
REV([D0000.01]);
[D0200] = MAX([D0100], [D0110], [D0120], [D0130], [D0140]);
[D0200] = MIN([D0100], [D0110], [D0120], [D0130], [D0140]);
[D0010] = EXP([D0020]);
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......