FT9Y-B1378
General Specifications
AC Power Type
Note 1:
Use in environments that satisfy product specifications.
Note 2:
UL, c-UL Listed at 0 to +50°C (FT1A Version V110).
Note 3:
Supports input/output overvoltage protection. When overvoltage protection occurred, the power supply output is shut off. In this situation,
shut off the AC input, wait for one minute or longer, and then turn on the AC input again.
Type Number
FT1A-
H12RC, B12RC
H24RC, B24RC
H40RC, B40RC
H48KC, H48SC
B48KC, B48SC
Normal Operating Conditions
Operating Temperature
0 to +55°C (operating ambient temperature) (Note 2)
Storage Temperature
–25 to +70°C (no freezing)
Relative Humidity
10 to 95% (non-condensing, operating and storage humidity)
Pollution Degree
2 (IEC60664-1)
Degree of Protection
IP20 (IEC60529)
Corrosion Immunity
Atmosphere free from corrosive gases
Altitude
Operation: 0 to 2,000m (0 to 6,565 feet)
Transport: 0 to 3,000m (0 to 9,840 feet)
Installation Location
Inside cabinet (Note 1)
Device Class
Open equipment
Overvoltage Category
II
Vibration Resistance
When mounted on a DIN rail or panel surface:
5 to 8.4Hz amplitude 3.5mm, 8.4 to 150Hz acceleration 9.8m/s
2
(1G)
2 hours per axis on each of three mutually perpendicular axes
Shock Resistance
147 m/s
2
(15G), 11ms duration, 3 shocks per axis on three mutually perpendicular axes
Power Supply (Note 3)
Rated Power Voltage
100 to 240V AC
Allowable Voltage Range
85 to 264V AC
Rated Power Frequency
50/60Hz (47 to 63Hz)
Maximum Power Consumption
18VA
41VA
48VA
43VA
Allowable Momentary Power Interruption
10ms maximum (at the rated power voltage)
Dielectric Strength Voltage
Between power and PE terminals: 1,500V AC, 1 minute
Between input and PE terminals: 1,500V AC, 1 minute
Between transistor output and PE terminals: 1,500V AC, 1 minute
Between relay output and PE terminals: 2,300V AC, 1 minute
Between power and input terminals: 1,500V AC, 1 minute
Between power and transistor output terminals: 1,500V AC, 1 minute
Between power and relay output terminals: 2,300V AC, 1 minute
Between input and transistor output terminals: 1,500V AC, 1 minute
Between input and relay output terminals: 2,300V AC, 1 minute
EMC Immunity
IEC/EN 61131-2:2007 compliant
Inrush Current
35A maximum (Cold start with T
a
= 25°C, 200V AC)
Ground
D-type ground (Class 3 ground)
Grounding Wire
UL1007 AWG16
Power Supply Wire
UL1015 AWG22, UL1007 AWG18
Effect of Improper Power Supply
Connection
Reverse polarity: Normal operation
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection: Permanent damage may be caused
Weight
Approx. 230g
Approx. 400g
Approx. 580g
Approx. 540g
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......