S
MART
AXIS P
RO
/ L
ITE
U
SER
'
S
M
ANUAL
FT9Y-B1378
5-51
5: S
PECIAL
F
UNCTIONS
Upload Settings
The SmartAXIS module user program can be uploaded to the memory cartridge. First configure the settings for the memory
cartridge to automatically upload the user program from the SmartAXIS module in WindLDR. If a user program already exists on
the memory cartridge, the user program on the memory cartridge is deleted and the upload settings are configured. When a
memory cartridge configured with upload settings is inserted in the SmartAXIS and the power is turned on, the user program on
the SmartAXIS module is automatically uploaded to the memory cartridge. The upload to the memory cartridge configured with
upload settings is valid only one time. To upload the user program again, configure the settings for the memory cartridge to
automatically upload the user program. For the SmartAXIS Pro, the user program on the SmartAXIS module can be uploaded to
the memory cartridge with the LCD and operation buttons. If a user program already exists on the memory cartridge, the user
program on the memory cartridge is deleted and the user program is uploaded.
Programming WindLDR
1.
Insert the memory cartridge into the SmartAXIS, turn the power on, and then connect the SmartAXIS to the computer
(WindLDR).
2.
From the WindLDR menu bar, select
Online
>
Upload
>
Memory Cartridge Upload
.
The Memory Cartridge Upload dialog box is displayed.
Note:
If the user program on the SmartAXIS to upload is password protected, click
Password
and enter the password.
3.
Click
OK
.
The user program on the memory cartridge is deleted at this time.
4.
Turn off the SmartAXIS power and remove the memory cartridge.
This concludes configuring the settings for the memory cartridge to upload the user program from the SmartAXIS.
5.
Insert the memory cartridge with the completed upload settings into the SmartAXIS and turn the power on.
The user program is automatically uploaded from the SmartAXIS module to the memory cartridge.
Notes:
In the following situations, a memory cartridge transfer error will occur. If the error occurs, the user program is not uploaded to the memory
cartridge, and SmartAXIS operation stops.
When the SmartAXIS user program upload protection is set to
Prohibited
When the SmartAXIS user program password protection is set and the memory cartridge password does not match
For user program protection, see "User Program Protection" on page 5-64.
User Program Passwords
When password protection is configured for the SmartAXIS module user program, uploads and downloads only happen when the
password configured for the memory cartridge and the SmartAXIS module user program password match.
For user program protection, see "User Program Protection" on page 5-64.
Type
Password match
Password does not match
SmartAXIS Pro
Enter the password with the module's LCD and
operation buttons.
Enter the password with the module's LCD and
operation buttons.
SmartAXIS Lite
Automatic upload/download
Automatic upload/download not possible
Summary of Contents for SmartAXIS FT9Z-1A01
Page 1: ...FT9Y B1378 7...
Page 10: ...TABLE OF CONTENTS Preface 9 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 212: ...7 DEVICE ADDRESSES 7 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 230: ...8 INSTRUCTIONS FUNCTION BLOCKS REFERENCE 8 18 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 344: ...13 SCRIPTS 13 36 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378...
Page 386: ...APPENDIX Appendix 16 SMARTAXIS PRO LITE USER S MANUAL FT9Y B1378 Japanese Font JIS X0201...
Page 393: ......