![IDEC microsmart pentra Programming Manual Download Page 92](http://html.mh-extra.com/html/idec/microsmart-pentra/microsmart-pentra_programming-manual_617383092.webp)
6: M
OVE
I
NSTRUCTIONS
6-14
FT1A S
MART
A
XIS
U
SER
’
S
M
ANUAL
FT9Y-B1382
NRS (N Data Repeat Set)
Applicable CPU Modules
Valid Devices
For the valid device address range, see pages 6-1 and 6-2
(Basic Vol.).
For the N-W, 1 word (16 bits) is always used without regard to the data type.
Special internal relays cannot be designated as D1.
When T (timer) or C (counter) is used as N-W or S1, the timer/counter current value (TC or CC) is read out. When T (timer) or C (counter) is used
as D1, the data is written in as a preset value (TP or CP).
When F (float) data type is selected, only data register and constant can be designated as S1, and only data register can be designated as D1.
When F (float) data type is selected and S1 does not comply with the normal floating-point format, a user program execution error will result,
turning on special internal relay M8004 and ERR LED on the CPU module.
Make sure that the last destination data determined by D1+N-1 (word or integer data type) or D1+2N-2 (double-word, long, or float data type) is
within the valid device range. If the derived destination device is out of the valid device range, a user program execution error will result, turning on
special internal relay M8004 and ERROR LED on the CPU module. For user program execution errors, see Chapter 4 “User Program Execution Errors”
on page 4-21.
Valid Data Types
Example: NRS(F)
S1
D1, D2, D3, ... , Dn–1
When input is on, 16- or 32-bit data designated by S1 is set to N blocks of
destinations, starting with device designated by D1.
NRS(*)
N-W
*****
S1
*****
D1
*****
16-/32-bit data
S1
Source data for repeat set
First 16-/32-bit data
D1
Second 16-/32-bit data
D1+1 or D1+2
Third 16-/32-bit data
D1+2 or D1+4
Nth 16-/32-bit data
D1+N–1 or D1+2N–2
N blocks of 16-/32-bit data
N Data Repeat Set
FT1A-12
FT1A-24
FT1A-40
FT1A-48
FT1A-Touch
X
X
X
X
X
Device
Function
I
Q
M
R
T
C
D
Constant
Repeat
N-W (N blocks)
Quantity of blocks to move
X
X
X
X
X
X
X
X
—
S1 (Source 1)
First device address to move
X
X
X
X
X
X
X
X
—
D1 (Destination 1)
First device address to move to
—
X
X
X
X
X
—
—
W (word)
X
When a bit device such as I (input), Q (output), M (internal relay), or R (shift register) is designated as the source
or destination, 16 points (word or integer data type) or 32 points (double-word or long data type) are used.
When a word device such as T (timer), C (counter), or D (data register) is designated as the source or
destination, 1 point (word or integer data type) or 2 points (double-word, long, or float data type) are used.
I (integer)
X
D (double word)
X
L (long)
X
F (float)
X
D25·D26
D30 through D39
When input I0 is turned on, data of data registers D25·D26 designated by source device S1 is moved to 10
data registers starting with D30 designated by destination device D1.
D1
D30
N-W
5
I0
NRS(F)
S1
D25
SOTU
123.4
D25·D26
123.4
D32·D33
123.4
D30·D31
123.4
D34·D35
123.4
D36·D37
123.4
D38·D39
Summary of Contents for microsmart pentra
Page 1: ...FT1A SERIES FC9Y B1382 Ladder Programming Manual ...
Page 6: ...Preface 5 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 104: ...7 DATA COMPARISON INSTRUCTIONS 7 10 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 122: ...8 BINARY ARITHMETIC INSTRUCTIONS 8 18 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 138: ...10 SHIFT ROTATE INSTRUCTIONS 10 12 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 162: ...11 DATA CONVERSION INSTRUCTIONS 11 24 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 188: ...12 CALENDAR COMPARISON INSTRUCTIONS 12 26 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 198: ...15 REFRESH INSTRUCTIONS 15 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 202: ...16 INTERRUPT CONTROL INSTRUCTIONS 16 4 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...
Page 266: ...20 DUAL TEACHING TIMER INSTRUCTIONS 20 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 318: ...25 USER COMMUNICATION INSTRUCTIONS 25 22 FT1A SMARTAXIS USER S MANUAL FT9Y B1382 ...