2: P
RODUCT
S
PECIFICATIONS
2-8
FC6A S
ERIES
MICROS
MART
U
SER
’
S
M
ANUAL
FC9Y-B1722
(28) Ethernet Port 1 Cover
A removable cover that protects Ethernet Port 1. When using the Ethernet port, remove the Ethernet Port 1 cover.
(29) Power Supply Terminals Cover
An openable cover that protects the power supply terminals. Remove the dummy cartridge when connecting a digital I/O
cartridge, analog I/O cartridge, or communication cartridge.
(30) USB Port Cover
An openable cover that protects the USB port. When using the USB port, open the USB port cover.
(31) Communication Connector Protection Sticker
This sticker protects the communication connector. Remove the communication connector protection sticker when
connecting the HMI module.
Power Supply Specifications
■
AC Power Type
Type No.
FC6A-C16R1AE, FC6A-C24R1AE, FC6A-C40R1AE, FC6A-C40R1AEJ
Rated Operating Voltage
100 to 240V AC
Voltage Fluctuation Range
85 to 264V AC
Rated Power Frequency
50/60 Hz (47 to 63 Hz)
Maximum Power Consumption
Standalone
When Maximum Load is Connected
FC6A-C16R1AE
33 VA
54 VA
FC6A-C24R1AE
35 VA
61 VA
FC6A-C40R1AE
41 VA
74 VA
FC6A-C40R1AEJ
37 VA
74 VA
Allowable Momentary Power
Interruption
10 ms or longer (when rated power supply voltage)
Withstand Voltage
Between power and PE terminals: 1,500V AC, 1 minute
Between input and PE terminals: 1,500V AC, 1 minute
Between relay output and PE terminals: 2,300V AC, 1 minute
Between power and input terminals: 1,500V AC, 1 minute
Between power and relay output terminals: 2,300V AC, 1 minute
Between input and relay output terminals: 2,300V AC, 1 minute
Insulation Resistance
Between power and PE terminals: 100 M
Ω
or higher (500V DC insulation resistance tester)
Between input and PE terminals: 100 M
Ω
or higher (500V DC insulation resistance tester)
Between relay output and PE terminals: 100 M
Ω
or higher (500V DC insulation resistance tester)
Between power and input terminals: 100 M
Ω
or higher (500V DC insulation resistance tester)
Between power and relay output terminals: 100 M
Ω
or higher (500V DC insulation resistance tester)
Between input and relay output terminals: 100 M
Ω
or higher (500V DC insulation resistance tester)
Inrush Current
40 A maximum
Isolation
Between power terminal and internal circuit: Transformer isolated
Ground
D-type ground (Class 3 ground)
Grounding Wire
See "Recommended Ferrule List" on page 3-43
Power Supply Wire
See "Recommended Ferrule List" on page 3-43
Effect of Improper Power Supply
Connection
Reverse polarity: Normal operation
Improper voltage or frequency: Permanent damage may be caused
Improper lead connection: Permanent damage may be caused
Weight
FC6A-C16R1AE
370 g
FC6A-C24R1AE
420 g
FC6A-C40R1AE
560 g
FC6A-C40R1AEJ
560 g
Summary of Contents for MICROSmart FC6A Series
Page 1: ...B 1722 8 FC6A SERIES User s Manual...
Page 12: ...TABLE OF CONTENTS Preface 11 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 182: ...2 PRODUCT SPECIFICATIONS 2 152 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 434: ...8 INSTRUCTIONS REFERENCE 8 18 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 520: ...11 SD MEMORY CARD 11 54 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 554: ...13 TROUBLESHOOTING 13 26 FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722...
Page 567: ...FC6A SERIES MICROSMART USER S MANUAL FC9Y B1722 A 13 APPENDIX ASCII Character Code Table...