![IDEC MICROSmart FC5A Series User Manual Download Page 308](http://html.mh-extra.com/html/idec/microsmart-fc5a-series/microsmart-fc5a-series_user-manual_617369308.webp)
24:
AS
‐
I
NTERFACE
M
ASTER
C
OMMUNICATION
24
‐
36
FC5A
M
ICRO
S
MART
U
SER
’
S
M
ANUAL
FC9Y
‐
B1273
Configuration
Before
commissioning
the
AS
‐
Interface
master
module,
configuration
must
be
done
using
either
WindLDR
or
the
push
‐
buttons
on
the
front
of
the
AS
‐
Interface
master
module.
This
section
describes
the
method
of
configuration
using
WindLDR
.
For
configuration
using
the
pushbuttons,
see
Configuration
is
the
procedure
to
store
the
following
information
to
the
AS
‐
Interface
master
module
ROM.
A
list
of
slave
addresses
to
be
used
Configuration
data
to
specify
slave
types,
or
identification
codes
(ID,
I/O,
ID2,
ID1)
Parameters
(P3,
P2,
P1,
P0)
to
designate
the
slave
operation
at
power
‐
up
WindLDR
provides
two
options
for
configuration:
auto
configuration
to
execute
automatic
configuration
and
manual
con
‐
figuration
to
execute
configuration
according
to
the
data
selected
by
the
user.
Auto
Configuration
Auto
configuration
stores
the
current
slave
configuration
data
(LDS,
CDI,
PI)
to
the
AS
‐
Interface
master
module
ROM
(LPS,
PCD,
PP).
To
execute
auto
configuration,
press
Auto
Configuration
in
the
Configure
AS
‐
Interface
Master
dialog
box.
Auto
configuration
has
the
same
effect
as
the
configuration
using
the
pushbuttons
on
the
AS
‐
Interface
master
module.
Manual
Configuration
Manual
configuration
is
the
procedure
to
write
the
LPS,
PCD,
and
PP
desig
‐
nated
on
WindLDR
to
the
AS
‐
Interface
master
module
ROM.
LPS
is
automati
‐
cally
generated
by
WindLDR
based
on
the
value
for
PCD.
To
change
PCD
and
PP,
use
the
Configure
Slave
dialog
box.
Set
the
PCD
of
each
slave
to
the
same
value
as
its
CDI.
If
the
PCD
is
different
from
the
CDI
for
a
slave,
then
that
slave
does
not
function
correctly.
Set
FFFFh
to
the
PCD
of
vacant
slave
numbers.
After
entering
a
PCD
value
and
selecting
parameter
statuses,
click
OK
.
At
this
point,
the
configuration
data
are
not
stored
to
the
AS
‐
Interface
master
module
ROM.
To
store
the
changes,
click
Manual
Configuration
on
the
Configure
AS
‐
Interface
Master
dialog
box.
The
screen
display
of
the
Configure
AS
‐
Interface
Master
dialog
box
can
be
updated
using
Refresh
.
If
you
save
the
configuration
data
to
a
file,
you
can
open
the
file
to
configure
other
AS
‐
Interface
master
modules
using
the
same
data.
To
save
and
open
the
configuration
file,
click
File
Save
or
File
Open
.
If
the
configuration
command
is
not
processed
correctly,
the
error
message
“AS
‐
Interface
Master
Error”
and
an
error
code
will
appear.
See
If
the
error
message
“Configuration
failure.
Confirm
the
slave
setup,
and
perform
configuration
again.”
is
shown,
and
the
FLT
LED
is
on,
then
remove
the
cause
of
the
error,
referring
to
13,
and
repeat
configuration.
The
configuration
cannot
be
done
in
the
following
cases.
Slave
Configuration
Data
AS
‐
Interface
Master
Module
ROM
List
of
detected
slaves
(LDS)
Configuration
data
image
(CDI)
Parameter
image
(PI)
List
of
projected
slaves
(LPS)
Permanent
configuration
data
(PCD)
Permanent
parameter
(PP)
Error
Code
Description
1
An
error
was
found
on
the
expansion
I/O
bus.
2
While
the
AS
‐
Interface
master
module
was
in
offline
mode,
attempt
was
made
to
execute
auto
configu
‐
ration
or
manual
configuration.
7
While
slave
address
0
existed
on
the
bus,
attempt
was
made
to
execute
auto
configuration
or
manual
configuration.
The
AS
‐
Interface
master
module
is
in
local
mode.
Configuration
Permanent
Parameter
(PP)
PCD
LPS
FFFFh
0
Other
values
1
Summary of Contents for MICROSmart FC5A Series
Page 1: ...FC5A SERIES FC9Y B1273 1 User s Manual Advanced Volume ...
Page 2: ......
Page 8: ...Preface 6 FC5A MicroSmart User s Manual FC9Y B1273 ...
Page 14: ...TABLE OF CONTENTS vi FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 52: ...4 DATA COMPARISON INSTRUCTIONS 4 10 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 72: ...5 Binary Arithmetic Instructions 5 20 FC5A MicroSmart User s Manual FC9Y B1273 ...
Page 88: ...7 SHIFT ROTATE INSTRUCTIONS 7 12 FC5A MicroSmart User s Manual FC9Y B1273 ...
Page 112: ...8 DATA CONVERSION INSTRUCTIONS 8 24 FC5A MicroSmart User s Manual FC9Y B1273 ...
Page 138: ...11 PROGRAM BRANCHING INSTRUCTIONS 11 14 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 178: ...13 PULSE INSTRUCTIONS 13 32 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 202: ...14 PID INSTRUCTION 14 24 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 206: ...15 DUAL TEACHING TIMER INSTRUCTIONS 15 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 214: ...16 INTELLIGENT MODULE ACCESS INSTRUCTIONS 16 8 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 248: ...21 COMPUTER LINK COMMUNICATION 21 4 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 272: ...23 MODBUS TCP COMMUNICATION 23 10 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 332: ...25 EXPANSION RS232C RS485 COMMUNICATION 25 16 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...
Page 341: ...NOTE FC5A MICROSMART USER S MANUAL FC9Y B1273 1 ...
Page 342: ...NOTE 2 FC5A MICROSMART USER S MANUAL FC9Y B1273 ...