  Compatibility  table  (FC4A/5A  series  ->  FC6A  Plus) 

29 

  Function settings 

The available options for replacing of all setting items are shown in the table below. 

Yes: 

Setting that is replaced automatically 

Indirectly:  Setting that needs to be replaced manually 
No: 

Setting that cannot be replaced 

 

Replaceability

 

Function setting for FC4A/5A series

 

FC6A series specifications

 

Yes

 

Operation/stop control

 

A function switch setting is added.

 

Yes

 

Memory backup

 

Same with FC4A/5A series.

 

Indirectly

 

Special input

 

High-speed 
counter

 

Select from among six high-speed counter groups.

 

Yes

 

Catch input

 

They are automatically replaced with the same group numbers. However, 
change wiring because the input terminal numbers are different.

 

Yes

 

Interrupt input

 

Indirectly

 

Frequency 
measurement

 

Select it using the “Frequency measurement” function.

 

Yes

 

Input filter

 

Same with FC4A/5A series. 

Yes

 

Timer interruption

 

Same with FC4A/5A series. 

Indirectly/No*1

 

Communication port

 

Some of the communication modes cannot be replaced. *1

 

No

 

Communication refresh for ports 3 
to 7

 

No setting is required because communication refresh is performed regularly.

 

No

 

Communication option

 

It is not supported and cannot be used. Specify a constant as the slave 
number for each communication mode setting, or specify or select using the 
data resister.

 

No

 

Key matrix

 

It is not supported and cannot be used. Use Expansion I/O Modules.

 

No

 

Clock cartridge

 

A clock is built in the CPU Module. Because the correction value is written at 
the time of shipment, it is unnecessary to make the setting.

 

No

 

Memory cartridge

 

It is not supported and cannot be used. User programs can be 
uploaded/downloaded using an SD memory card. Make the setting from the 
setting window for the SD memory card.

 

No

 

Expansion Modules

 

An AS-Interface Module is not supported and cannot be used.

 

Yes

 

Device setting

 

Same with FC4A/5A series.

 

Yes

 

Program protection

 

The old password can also be used if the program protection is not changed.

 

No

 

Self-diagnosis

 

The RUN LED blinking setting is not supported and cannot be used.

 

Yes

 

Network setting

 

Same with FC4A/5A series.

 

Yes

 

E-mail setting

 

Same with FC5A series.

 

Yes

 

Network administration

 

The Ping setting will be converted in a millisecond unit.

 

Indirectly

 

Connection setting

 

Make the settings for connection 1 to 8 (commonly used for the server/client).

 

Yes

 

Web server

 

Same with FC5A series.

 

 
*1 

The following communication modes are not supported in the 

FC6A series

 and cannot be 

replaced. 
Modem communication, Modbus ASCII master/slave,   

          Replace with User Communication or Modbus RTU master/slave in manual.

 

 

  PID Module setting 

The PID Module set in the dialog for the FC5A series Expansion Module setting will be automatically 
converted when the model is changed to the FC6A series. The module series numbers before and 
after conversion are as follows. 

 

FC5A series No. 

FC6A series No. 

FC5A-F2MR2 

FC6A-F2MR1 

FC5A-F2M2 

FC6A-F2M1 

Summary of Contents for MICROSmart FC4A Series

Page 1: ...B 1943 2 From FC4A 5A series MICROSmart Programmable Controller to FC6A Plus CPU module Replacement Manual...

Page 2: ...er list 13 External dimensions 14 Wiring 201 Program conversion FC4A 5A series FC6A Plus 24 Compatibility table FC4A 5A series FC6A Plus 29 Function settings 29 PID Module setting 29 Basic instruction...

Page 3: ...eyond the basic number of I Os in some types of the FC4A 5A series However I Os can be expanded in all the CPU Modules of the FC6A Plus The Maximum I Os depends on the combination of Expansion Modules...

Page 4: ...8 pts input and 8 pts relay output 2A 4 pts COM0 4 pts COM1 21 7 15 2 63 3 224 480 2 2016 3 70 FC5A C10R2C 2 3K 700 FC4A C16R2C 2 5K 9 pts input and 7 pts relay output 2A 4 pts COM0 2 pts COM1 1 pts...

Page 5: ...FC6A D32K3CEE 16 pts input and 16 pts output transistor sink 0 1A 16 pts COM FC4A D20RS3 12 pts input and 6 pts output relay 2A 3 pts COM1 2 pts COM2 1 pts COM3 2 pts output transistor source 0 3A 2...

Page 6: ...input and 8 pts output transistor sink 0 5A 8 pts COM FC6A D16R1CEE 8 pts input and 8 pts output relay 2A 4 pts COM0 4 pts COM1 FC5A D16RS1 8 pts input and 6 pts output relay 2A 3 pts COM1 2 pts COM2...

Page 7: ...able Available Available Expansion interface module unibody type FC6A EXM2 Available Available Available Available N A Expansion interface module separate slave type FC6A EXM1S Available Available N A...

Page 8: ...T08K1 11 3 81 8 pts output transistor sink 0 3A 8 pts 1 common 23 5 FC6A T08K1 11 5 08 8 pts output transistor sink 0 5A 8 pts 1 common 23 6 Different FC4A T08S1 11 3 81 8 pts output transistor sourc...

Page 9: ...Voltage 0 to 10 V Current 4 to 20 mA Temperature measuring resistor Pt100 Pt1000 Ni100 Ni1000 Thermocouple K J T 50 000 23 5 FC6A J4CN1 4 Voltage 0 to 10 V Voltage 10 to 10 V Current 0 to 20 mA Curre...

Page 10: ...to 10 V Voltage 10 to 10 V Current 0 to 20 mA Current 4 to 20 mA 2 pts output Voltage 0 to 10 V Voltage 10 to 10 V Current 0 to 20 mA Current 4 to 20 mA 4 096 23 6 No change FC6A L03CN1 3 2 pts input...

Page 11: ...1 to 5 V 0 to 10 V Current 0 to 20 mA 4 to 20 mA Temperature measuring resistorThermocouple 2 pts output Voltage output 12 V Current output 4 to 20 mA Input 12 000 Output 1 000 23 5 FC6A F2M1 2 2 pts...

Page 12: ...cation range Communication speed Isolation from internal circuit Width mm FC5A SIF2 1 RS232C Max 10 m Max 115 2 Kbps Isolated 23 5 FC6A PC1 1 1 RS232C Terminals Max 5 m Max 115 2 Kbps Not isolated 42...

Page 13: ...Y307 FC4A D20K3 D20S3 X0 X13 X14 X27 Y0 Y7 Y10 Y27 X30 X187 Y30 Y187 FC4A D40K3 D40S3 X0 X27 Y0 Y17 Y20 Y27 X30 X307 Y30 Y307 FC5A D12K1E D12S1E X0 X7 X10 X27 Y0 Y3 Y4 Y27 X30 X627 Y30 Y627 FC5A D16RK...

Page 14: ...series MICROSmart All in One type CPU Modules FC4A C10R2 C16R2 FC4A C24R2 FC5A C10R2 C16R2 FC5A C24R2 Slim type CPU Modules FC4A D20 1 FC4A D40 3 FC5A D16R 1 FC5A D32 3 FC4A D20 3 FC5A D12 1E The dim...

Page 15: ...C4A L03A1 FC4A L03AP1 FC4A M08BR1 FC4A N08A11 FC4A N08B1 FC4A R081 FC4A T08K1 FC4A T08S1 FC4A K4A1 FC4A N16B3 FC4A T16K3 FC4A T16S3 FC4A N16B1 FC4A R161 FC4A J8C1 FC4A J8AT1 FC4A J4CN1 FC4A N32B3 FC4A...

Page 16: ...Optional Modules Expansion Interface Modules FC4A HPC1 FC4A HPC2 FC4A HPC3 FC4A HPH1 FC5A EXM1M FC5A EXM1S FC5A EXM2 1The dimension when the hook is pulled out is 8 5 mm 2 It is the standard length w...

Page 17: ...External dimensions 17 External dimensions of FC6A series MICROSmart Plus CPU Modules FC6A D16 1CEE FC6A D32 3CEE Unit mm...

Page 18: ...1 FC6A N08A11 FC6A J4A1 FC6A J8A1 FC6A J4CN1 FC6A J8CU1 FC6A L06A1 FC6A J4CH1Y FC6A N16B1 FC6A R161 FC6A T16K1 FC6A T16P1 FC6A SIF52 The dimension when the hook is pulled out is 9 3 mm FC6A F2MR1 FC6A...

Page 19: ...l Modules Expansion Interface Modules FC6A PH1 FC6A PC1 FC6A PC3 FC6A PN4 FC6A PJ2A FC6A PK2AV FC6A PTK4 FC6A PK2AW FC6A PJ2CP FC6A PTS4 FC6A HPH1 FC6A EXM1M FC6A EXM1S The dimension when the hook is...

Page 20: ...External dimensions 20 FC6A EXM2 The dimension when the hook is pulled out is 9 3 mm...

Page 21: ...erminal blocks are used for all the terminals of the FC4A 5A Slim type except the power supply terminal Removable terminal blocks are used for all the FC4A 5A series expansion modules except FC4A M24B...

Page 22: ...8 AI 0 75 8 for 1 wire connection AI TWIN 2 x 0 75 8 for 2 wire connection UL1007AWG22 AI 0 34 8 for 1 wire connection UL1007AWG20 AI 0 5 8 for 1 wire connection AI TWIN 2 x 0 5 8 for 2 wire connectio...

Page 23: ...0 34 8 for 1 wire connection UL1007AWG20 AI 0 5 8 for 1 wire connection AI TWIN 2 x 0 5 8 for 2 wire connection UL1007AWG18 AI 0 75 8 for 1 wire connection AI TWIN 2 x 0 75 8 for 2 wire connection UL1...

Page 24: ...should be performed according to the WindLDR model setting For details refer to Conversion procedure in page 25 When the model is changed commands which can be replaced automatically are converted bu...

Page 25: ...upload read out the program The procedure is as follows Click Upload in the Online tab of WindLDR The upload window will appear Click OK Conversion procedure Open the program for the FC4A 5A series us...

Page 26: ...t which can be checked on the information window When the mouse cursor is put on each item of the conversion report in the information window to select the item the cursor in the ladder program field...

Page 27: ...he Home tab and further select Replace 2 In the displayed window enter the I O numbers before and after conversion in Device and the I O points to be converted in Points to Replace If comments should...

Page 28: ...o be converted and the confirmation window will appear To convert while confirming I Os one by one click Yes To convert the remaining I Os at a time without confirming them click Yes to all The cursor...

Page 29: ...annot be used Use Expansion I O Modules No Clock cartridge A clock is built in the CPU Module Because the correction value is written at the time of shipment it is unnecessary to make the setting No M...

Page 30: ...with FC4A 5A series Yes AND LOD Same with FC4A 5A series Yes OR LOD Same with FC4A 5A series Yes BPS Same with FC4A 5A series Yes BRD Same with FC4A 5A series Yes BPP Same with FC4A 5A series Yes TML...

Page 31: ...eries Yes ADD SUB Same with FC4A 5A series Yes MUL Same with FC4A 5A series Yes DIV Same with FC4A 5A series Yes ROOT Same with FC4A 5A series Yes INC DEC Same with FC4A 5A series Yes SUM Same with FC...

Page 32: ...FC4A 5A series Yes TTIM Same with FC4A 5A series Yes LABEL Same with FC4A 5A series Yes LJMP Same with FC4A 5A series Yes LCAL Same with FC4A 5A series Yes LRET Same with FC4A 5A series Yes DJNZ Same...

Page 33: ...FC4A K4A1 FC6A K4A1 FC4A L03A1 FC6A L03CN1 FC4A L03AP1 Refer to 1 for precautions on model conversion of Analog Modules Yes PULSST Same with FC4A 5A series Yes PWMST Same with FC4A 5A series Yes RAMP...

Page 34: ...odule uses the built in clock which cannot be stopped M8015 is defined as reserved Yes M8016 Calendar Data Write Flag Same with FC4A 5A series Yes M8017 Clock Data Write Flag Same with FC4A 5A series...

Page 35: ...No M8064 Modem Mode General Command AT Command Completion No M8065 Modem Mode Answer Initialization String Completion No M8066 Modem Mode Answer ATZ Completion No M8067 Modem Mode Operational State N...

Page 36: ...letion Relay Same with FC4A 5A series Yes M8115 Data Link Slave Station 30 Communication Completion Relay Same with FC4A 5A series Yes M8116 Data Link Slave Station 31 Communication Completion Relay S...

Page 37: ...X2 Current Value Underflow Indirectly M8163 High speed Counter X5 X7 Current Value Overflow There is no compatibility with the high speed counter Set and refer to the high speed counter group 5 I6 nea...

Page 38: ...o M8207 User Communication Receive Instruction Cancel Flag Connection 1 to 8 M8210 to M8211 Reserved Reserved Indirectly M8212 to M8214 Maintenance Communication Server 1 to 3 Status There is no compa...

Page 39: ...te only Same with FC4A 5A series Yes D8020 Minute New Data Write only Same with FC4A 5A series Yes D8021 Second New Data Write only Same with FC4A 5A series Yes D8022 Constant Scan Time Preset Value S...

Page 40: ...Make the setting in the communication setting for the Modbus master request table No D8055 Current Pulse Frequency of PULS1 or RAMP1 Y0 It cannot be used because the frequency band that can be output...

Page 41: ...at Master Station Error station number and error code at Modbus Master Indirectly D8071 Indirectly D8072 Indirectly D8073 Indirectly D8074 Indirectly D8075 Indirectly D8076 Indirectly D8077 Indirectly...

Page 42: ...ommand Result Code Modem mode is not supported and cannot be used Special data registers are defined as follows D8115 to D8119 Reserved D8120 to D8121 HMI Module Information D8122 to D8127 Cartridge S...

Page 43: ...not supported and cannot be used Expansion module I O refresh is performed by the CPU Module It is not performed by the Expansion Interface Module D8252 is defined as reserved D8253 to D8277 Reserved...

Page 44: ...Indirectly D8354 to D8357 Maintenance Communication Server 2 Connected IP Address Indirectly D8358 to D8361 Maintenance Communication Server 3 Connected IP Address Indirectly D8362 to D8365 Server Co...

Page 45: ...eserved D8429 to D8431 Refer to HMI Module connection information No D8422 Maintenance Communication Server 2 Port Number of Client No D8423 Maintenance Communication Server 3 Port Number of Client No...

Page 46: ...ts 900 pts 1 When a 64 KB memory cartridge is used 2 The download function cannot be used during running 3 Non Retentive Data Register The following table shows the comparison of the I O number betwee...