L
ON
W
ORKS
I
NTERFACE
M
ODULE
O
PEN
N
ET
C
ONTROLLER
L
ON
W
ORKS
I
NTERFACE
M
ODULE
U
SER
’
S
M
ANUAL
7
Terminator
Terminators must be connected to the L
ON
W
ORKS
network. When setting up a network, connect one or two terminators
depending on the topology. The terminator consists of one resistor and two capacitors as illustrated below:
Bus Topology
Connect terminators to the both ends of the bus topology network.
Free Topology
Connect a terminator to any position on the free topology network.
R
105
Ω
, 1%, 1/8W
C1 and C2
100 µF,
≥
50V (note the polarity)
R
52.3
Ω
, 1%, 1/8W
C1 and C2
100 µF,
≥
50V (note the polarity)
+
R
C1
C2
Network
+
Terminator Configuration
Terminator
Terminator
Node
Node
Node
Node
Node
Node
Node
Terminator
Node
Node
Node
Node
Node
Node
Node