Functions
HR9Z-B2202 8/2020
61
Application Function 2
Synchronization:
Characteristic
Value/Description
Typical applications
Monitoring of Emergency Stop circuits as per
ISO 13850 and IEC 60204-1, stop category 0
Monitoring of guards as per ISO 14119/14120
with electrical switches
Type of outputs of sensor/device providing the input signal
for application function
Normally open, normally closed and/or changeover
outputs
S## terminals to be connected
S11-S12 and S21-S22 for sensor/device A
S11-S13 and S21-S23 for sensor/device B
Dynamization
Yes
Signal interlock monitoring
Between terminals S12 and S22
Between terminals S13 and S23
Synchronized terminals
Synchronization time
S12 synchronized with S22
If S12 is activated before S22, S22 has to be activated
within 2 s.
If S22 is activated before S12, S12 has to be activated
within 4 s.
S13 synchronized with S23
If S13 is activated before S23, S23 has to be activated
within 2 s.
If S23 is activated before S13, S13 has to be activated
within 4 s.
Wiring of the inputs for Emergency Stop
Wiring of the inputs for guards