Functions
HR9Z-B2200 8/2020
73
Start Functions
Overview
The device provides several start functions which are selected by means of the start function
selector. The start function determines the start behavior of the device after power-on and for a
transition from the operating state Run: Outputs Deenergized (defined safe state) to the operating
state Run: Outputs Energized.
The start behavior is configured using the following characteristics:
Type of start (automatic/manual start and monitored start)
With or without startup test
With or without dynamization
Refer to the chapter Electrical Installation
) for additional information on wiring the
start input.
WARNING
UNINTENDED EQUIPMENT OPERATION
Do not use the Start function for safety-related purposes.
Use Monitored Start or Startup Test if unintended restart is a hazard according to your risk
assessment.
Failure to follow these instructions can result in death, serious injury, or equipment damage.
Summary of Contents for HR6S-DN
Page 1: ...http www idec com HR6S DN Safety Module Original instructions HR9Z B2200...
Page 8: ...8 HR9Z B2200 8 2020...
Page 14: ...14 HR9Z B2200 8 2020...
Page 20: ...Introduction 20 HR9Z B2200 8 2020...
Page 56: ...Installation 56 HR9Z B2200 8 2020...
Page 64: ...Functions 64 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Page 66: ...Functions 66 HR9Z B2200 8 2020 Wiring of the inputs for coded magnetic switches...
Page 69: ...Functions HR9Z B2200 8 2020 69 Wiring of the inputs for sensors devices with two PNP outputs...
Page 72: ...Functions 72 HR9Z B2200 8 2020 Wiring of the inputs for sensors devices with OSSD outputs...
Page 98: ...Accessories Service Maintenance and Disposal 98 HR9Z B2200 8 2020...