Slave Address Shading Colors
Operating status of the slave can be confirmed by viewing the shading color at the slave address on the Configure AS-
Interface Master dialog box. The screen display can be updated by clicking the
Refresh
button.
Change Slave Address
When a slave is connected to the AS-Interface master module, the slave address can be changed using
WindLDR
.
To change a slave address, from the
WindLDR
menu bar, select
Configure
>
AS-Interface Master
. The Configure AS-Interface Master dialog box
appears.
Click a slave address to open the Change Slave Address dialog box. Select
Slave A or Slave B, enter a required address in the New Address field, and
click
OK
. The Change Slave Address dialog box is closed. The new slave
address is stored in the slave module nonvolatile memory.
If the command is not processed correctly, the error message “AS-Interface Master Error” and an error code will appear.
See page 28-34.
The address cannot be changed in the following cases.
Address Shading
Description
LAS
List of
active
slaves
LDS
List of
detected
slaves
LPF
List of
peripheral
fault slaves
LPS
List of
projected
slaves
No Shade
The slave is not recognized by the master.
OFF
OFF
OFF
ON/OFF
Blue Shade
The slave is active.
ON
ON
OFF
ON
Yellow Shade
The slave is recognized but not enabled to operate.
OFF
ON
OFF
OFF
Red Shade
An error was found in the slave.
ON/OFF
ON/OFF
ON
ON/OFF
•
Duplicate slave addresses
Each slave must have a unique address. Do not connect two or more slaves with the same address,
otherwise the AS-Interface master module cannot locate the slave correctly. When two slaves have the
same address and different identification codes (ID, I/O, ID2, ID1), the AS-Interface master module
detects an error. When two slaves have the same address and same identification codes, the AS-Inter-
face master module cannot detect an error. Failure to observe this warning may cause severe personal
injury or heavy damage to property.
•
When a slave with address 0 is connected to the AS-Interface master module, power up the
Micro-
Smar t
CPU module first. Approximately 5 seconds later, turn on the AS-Interface power supply. If
the CPU module and AS-Interface power supply are turned on at the same time, the AS-Interface
master module enters normal protected offline. In this mode, slave addresses can be changed, but
the slave status cannot be confirmed on
WindLDR
.
Error Code
Description
1
•
An error was found on the expansion I/O bus.
7
•
The AS-Inter face master module is in local mode.
8
•
The slave you are tr ying to change does not exist.
•
A slave of the designated new address already exists.
•
While a standard slave was set at A address, attempt was made to set an A/B slave at B
address of the same number.
•
While an A/B slave was set at B address, attempt was made to set a standard slave at A
address of the same number.
Warning
Caution
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...