23: I
NTELLIGENT
M
ODULE
A
CCESS
I
NSTRUCTIONS
23-2
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
RUNA READ (Run Access Read)
Applicable CPU Modules
Valid Operands (Run Access Read)
For the valid operand number range, see pages 6-1 and 6-2.
DATA:
Specify the first operand number to store the data read from the intelligent module.
▲
Internal relays M0 through M1277 and AS-Interface internal relays M1300 through M1997 can be desig-
nated as DATA. Special internal relays cannot be designated as DATA.
When T (timer) or C (counter) is used as DATA for Run Access Read, the data read from the intelligent
module is stored as a preset value which can be 0 through 65535.
All data registers, including special data registers, AS-Interface data registers, and expansion data registers,
can be designated as DATA.
STATUS:
Specify a data register to store the operating status code. Only data registers D0 through D1299 can be des-
ignated as STATUS. Special data registers, AS-Interface data registers, and expansion data registers
cannot
be designated whether the AS-Interface master module is used or not. For status code description, see
page 23-6.
SLOT:
Enter the slot number where the intelligent module is mounted. A maximum of seven intelligent modules
can be used.
ADDRESS:
Specify the first address in the intelligent module to read data from.
BYTE:
Specify the quantity of data to read in bytes.
The RUNA READ instruction cannot be used in an interrupt program. If used, a user program execution error will result,
turning on special internal relay M8004 and the ERR LED on the CPU module.
Valid Data Types
FC4A-C10R2/C
FC4A-C16R2/C
FC4A-C24R2/C
FC4A-D20K3/S3
FC4A-D20RK1/RS1 & FC4A-D40K3/S3
—
—
X
X
X
Operand
Function
I
Q
M
R
T
C
D
Constant
Repeat
DATA
First operand number to store read data
—
X
▲
X
X
X
X
—
—
STATUS
Operating status code
—
—
—
—
—
—
X
—
—
SLOT
Intelligent module slot number
—
—
—
—
—
—
—
1-7
—
ADDRESS
First address in intelligent module to read data from
—
—
—
—
—
—
—
0-127
—
BYTE
Bytes of data to read
—
—
—
—
—
—
—
1-127
—
W (word)
I (integer)
X
X
While input is on, data is read from the area
star ting at ADDRESS in the intelligent module
designated by SLOT and stored to the operand
designated by DATA.
BYTE designates the quantity of data to read.
STATUS stores the operating status code.
DATA
*****
SLOT
*
STATUS
*****
BYTE
***
ADDRESS
***
RUNA(*)
READ
When a bit operand such as I (input), Q (output), M (internal relay), or R (shift register) is
designated as DATA, 16 points are used.
When a word operand such as T (timer), C (counter), or D (data register) is designated as
DATA, 1 point is used.
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...