4: O
PERATION
B
ASICS
« FC4A M
ICRO
S
MART
U
SER
’
S
M
ANUAL
»
4-3
Start/Stop Operation
This section describes operations to start and stop the
MicroSmart
and to use the stop and reset inputs.
Start/Stop Schematic
The start/stop circuit of the
MicroSmart
consists of
three blocks; power supply, M8000 (start control spe-
cial internal relay), and stop/reset inputs. Each block
can be used to start and stop the
MicroSmart
while
the other two blocks are set to run the
MicroSmart
.
Start/Stop Operation Using WindLDR
The
MicroSmart
can be started and stopped using
WindLDR
run on a Windows PC connected to the
MicroSmart
CPU
module. When the
PLC Start
button is pressed in the dialog box shown below, start control special internal relay M8000
is turned on to start the
MicroSmart
. When the
PLC Stop
button is pressed, M8000 is turned off to stop the
MicroSmart
.
1.
Connect the PC to the
MicroSmart
, start
WindLDR
, and power up the
MicroSmart
2.
Check that a stop input is not designated using
Configure
>
Function Area Settings
>
Run/Stop
Note:
When a stop input is designated, the
MicroSmart
cannot be star ted or stopped by turning star t control special inter-
nal relay M8000 on or off.
3.
Select
Online
from the
WindLDR
menu bar, then select
Download Program
. Or, click the download icon
.
The Download Program dialog box appears.
4.
Click the
PLC Start
button to start operation, then the start control special internal relay M8000 is turned on.
5.
Click the
PLC Stop
button to stop operation, then the start control special internal relay M8000 is turned off.
The PLC operation can also be started and stopped while
WindLDR
is in the monitor mode. To access the
Start
or
Stop
button, select
Online
>
Monitor
and select
Online
>
PLC Status
>
Run/Stop Status
.
Note:
Special internal relay M8000 is a keep type internal relay and stores the status when power is turned off. M8000
retains its previous status when power is turned on again. However, when the backup batter y is dead, M8000 loses the
stored status, and can be turned on or off as programmed when the
MicroSmart
is powered up. The selection is made in
Configure
>
Function Area Settings
>
Run/Stop
>
Run/Stop Selection at Memory Backup Error
The backup duration is approximately 30 days (typical) at 25°C after the backup battery is fully charged.
•
Make sure of safety before starting and stopping the
MicroSmart
. Incorrect operation on the
MicroSmart
may cause machine damage or accidents.
Caution
Power
Supply
M8000
Stop
Input
Reset
Input
Star t
Star t Control
PLC
WindLDR
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...