Slim Type CPU Module (DC Power)
Power Supply Voltage
The allowable power voltage range for the slim type
MicroSmart
CPU module is 20.4 to 26.4V DC.
Power failure detection voltage depends on the quantity of used input and output points. Basically, power failure is
detected when the power voltage drops below 20.4V DC, stopping operation to prevent malfunction.
A momentary power interruption for 10 ms or less is not recognized as a power failure at the rated voltage of 24V DC.
Inrush Current at Power-up
When the slim type CPU module is powered up, an inrush current of a
maximum of 50A flows.
Power Supply Wiring
Use a stranded wire of UL1015 AWG22 or UL1007 AWG18 for power
supply wiring. Make the power supply wiring as short as possible.
Run the power supply wiring as far away as possible from motor lines.
Grounding
To prevent electrical shocks, connect the
terminal to a proper ground
using a wire of UL1015 AWG22 or UL1007 AWG18. The grounding also
prevents malfunctioning due to noise.
Do not connect the grounding wire in common with the grounding wire of
motor equipment.
Caution
•
Use a power supply of the rated value. Use of a wrong power supply may cause fire hazard.
•
The allowable power voltage range for the slim type
MicroSmart
CPU module is 20.4 to 26.4V
DC. Do not use the
MicroSmart
on any other voltage.
•
If the power voltage turns on or off very slowly between 10 to 15V DC, the
MicroSmart
may run
and stop repeatedly between these voltages. If failure or disorder of the control system, damage,
or accidents may be caused, provide a measure for prevention using a voltage monitoring circuit
outside the
MicroSmart.
•
Use an IEC 60127-approved fuse on the power line outside the
MicroSmart
. This is required
when equipment containing the
MicroSmart
is destined for Europe.
24V DC
+ –
+
–
Summary of Contents for FC4A-C10R2
Page 1: ...FC4A SERIES Micro Programmable Logic Controller User s Manual FC9Y B812 ...
Page 6: ...PREFACE 4 FC4A MICROSMART USER S MANUAL ...
Page 94: ...2 MODULE SPECIFICATIONS 2 74 FC4A MICROSMART USER S MANUAL ...
Page 184: ...6 ALLOCATION NUMBERS 6 20 FC4A MICROSMART USER S MANUAL ...
Page 218: ...8 ADVANCED INSTRUCTIONS 8 8 FC4A MICROSMART USER S MANUAL ...
Page 240: ...11 BINARY ARITHMETIC INSTRUCTIONS 11 8 FC4A MICROSMART USER S MANUAL ...
Page 244: ...12 BOOLEAN COMPUTATION INSTRUCTIONS 12 4 FC4A MICROSMART USER S MANUAL ...
Page 252: ...13 SHIFT ROTATE INSTRUCTIONS 13 8 FC4A MICROSMART USER S MANUAL ...
Page 274: ...15 WEEK PROGRAMMER INSTRUCTIONS 15 8 FC4A MICROSMART USER S MANUAL ...
Page 378: ...22 DUAL TEACHING TIMER INSTRUCTIONS 22 4 FC4A MICROSMART USER S MANUAL ...
Page 386: ...23 INTELLIGENT MODULE ACCESS INSTRUCTIONS 23 8 FC4A MICROSMART USER S MANUAL ...
Page 408: ...24 ANALOG I O CONTROL 24 22 FC4A MICROSMART USER S MANUAL ...
Page 426: ...26 COMPUTER LINK COMMUNICATION 26 6 FC4A MICROSMART USER S MANUAL ...