VoltAware™ Non-Contact Voltage (NCV) Tester
Instruction Sheet
IMPORTANT SAFETY INFORMATION
Read
and
understand
all of the instructions and safety information in these operating instructions before
using this tester.
WARNINGS
To avoid possible electric shock, personal injury or death follow these guidelines:
• Do not use if green light is not illuminating on tester.
• Do not use if tester appears damaged or is not operating properly.
• Do not use tester for more than the rated voltage on the tester.
• Do not use without the tester fully assembled.
• This tester will not detect the presence of DC voltage.
• This tester will not detect voltages at a distance, such as through walls, metal conduit, or shielded wire.
• Voltage detection maybe affected by outlet design, insulation thickness/type.
• Do not assume that no voltage indication means the circuit is de-energized.
• Voltages below 50VAC will not be detected by the 61-025 but are still shock hazards that can result
in injury or death.
• Use the 3 Point Safety Method. (1) Verify tester operation by measuring a known voltage. (2) Apply tester to circuit under test. (3) Return to the known live voltage again to ensure
proper operation.
• Ensure all fingers are behind finger guard when testing for voltage.
• Replace batteries as soon as low battery is indicated.
• If this tester is used in a manner not specified by IDEAL, protection provided by the product may be impaired.
• Comply with local and national safety requirements, including the use of appropriate personal protective equipment.
Features:
The VoltAware™ NCV tester is useful for identifying hot conductors, finding breaks in wires and detecting the presence of AC voltage at outlets, switches, electrical panels, wires and cables.
• 61-025 model indicates presence of voltage from 50-1000VAC
• 61-026 model indicates presence of voltage from 12-90VAC
• Visual indication of voltage
• Selectable Audible indication of voltage
• Low Battery Indicator
• Sleek, compact design
Operation:
• Twist the tester body to the On position.
• Verify the green light is on.
• Verify tester operation on a known voltage source.
• Place the tip of the tester near an AC voltage source to obtain a voltage indication.
• Voltage presence is indicated by a red, flashing light.
Selectable On/Off for Audible Beeper:
• The tester defaults to the audible ON mode.
• To turn the audible Off, depress the dark gray button.
• To turn the audible back On, depress the button again.
Low Battery Indicator:
• When the battery voltage drops below 2V, the tester indicates the low battery condition by turning off the green light.
Battery Replacement:
• With the tester in the Off position, pull lightly on the two case halves. The tester should separate slightly.
• Then, with little force, twist the two halves away from each other slightly as in the figure. Then, pull the two case
halves apart. Replace with 2 AAA (LR03) batteries.
• Reverse process to re-assemble tester.
Maintenance:
Clean with a damp cloth and mild detergent. If the tester acts erratically, or the green light is not on,
change the batteries.
Service and Replacement Parts:
There are no user-serviceable parts. To inquire about service information, contact IDEAL INDUSTRIES, INC.
at 877-201-9005, or visit our website at www.testersandmeters.com.
Specifications:
Voltage Range:
50-1000VAC (61-025)
12-90VAC (61-026)
Frequency Range:
50-500 Hz
Operating Environment:
32 to 122°F (0 to 51°C)
at <95% R.H.
Storage Temp.:
-4 to 140°F (-20 to 60°C)
at <95% R.H.
Battery:
(2) 1.5V AAA batteries (IEC LR03)
Altitude:
9843 ft. (3000m)
Dimensions:
6.0” (H) x 0.75” (D) [152mm (L) x 19mm (D)]
Weight:
1.6 oz. (46g)
Safety
Complies with UL-61010, EN61010, Cat IV-1000V
Equipment protected by double insulation.
Instrument complies with insulation overvoltage category IV. Cat IV equipment is designed to protect against transients from primary supply level. Pollution degree 2 in accordance with
#61-025
#61-026
!
C
US
N12966
Vo
ltA
ware
ON
OF
F
#6
1-
025
Cat I
V 5
0-1
000V
AC
OFF
ON
#61-025
50-1000VAC
OFF
ON
#61-025
50-1000VAC
#61-025
at IV 50-1000VAC
OFF
ON
OFF
ON
+
–
+
–
#61-025
Cat IV 50-1000VAC
ND 6336-1 61-025 VoltAware Ins. 1/4/07 12:57 PM Page 1