PRT-ATH1 / ACC-ATH1
Protege Temperature and Humidity Sensor
Installation Manual | April 2011
13
Technical Specifications
The following technical specifications are important and vital to the correct operation of the Protege Temperature
and Humidity Sensor. Failure to adhere to the technical specifications will result in any warranty or guarantee that
was provided becoming NULL AND VOID.
Integrated Control Technology continually strives to increase the performance of its products and as a result the
specifications may change without notice.
It is recommended that you always consult www.incontrol.co.nz for
the latest documentation and product information.
Operating Voltage
12VDC (8 to 30VDC)
Operating Current
20mA (Typical)
Internal Temperature Range
-40˚C to 60˚C (±1˚C) (-40˚F to 140.0˚F (±2˚F))
External Temperature Range (Thermocouple)
-40˚C to 60˚C (±1˚C) (-40˚F to 140.0˚F (±2˚F))
Humidity Range
0% to 100% (±3%)
Communication
Non-isolated
Zone Inputs
8 Trouble Zones
PGM Outputs
2x Relay Outputs (100mA max)
2x Configurable LED Outputs
PGM Outputs (ACC-ATH1 only)
2x 4-20mA or 0-10V Analog Outputs
Operating Temperature
5˚ to 55˚C (41˚ to 131˚F)
Storage Temperature
-10˚ to 85˚C (14˚ to 185˚F)
Humidity
0% to 85% (non condensing)
Dimensions (H x W x D)
118 x 75 x 19mm (4.7 x 3 x 0.75”)
Weight
118g (4.16oz)
The size of conductor used for the supply of power to the Protege Temperature and Humidity Sensor should be
adequate in size to prevent voltage drop at the power terminals of no more than 5% of the rated supply voltage.
Specifications are subject to change without notice, please visit www.incontrol.co.nz for the latest information.