Innovative Circuit Technology Ltd.
20
3.5. Administrator Password / IP Address Reset
This procedure resets the Administrator password, IP address, and
port settings to the original factory default values. The Standard User
password is not affected. To reset, do the following:
1.
In the Control Panel menu on the front of the power supply, go to
the Comm Settings screen and press the Enter key.
2.
Scroll down to Reset Comm Settings and press the Enter key.
3.
Turn the Encoder Wheel to select Yes, and then press the Enter
key.
4.
After reset is complete, go to the Network Status screen in the
Control Panel menu to view the new IP address of the power
supply.
4. SMART PARALLEL OPERATION
If your load requires more power than can be supplied by a single
ICT Digital Series power supply, two or more power supplies
(maximum 6) of the same output voltage rating can be connected in
parallel in a Master-Slave configuration to increase the power
available, using the SHARE ports on the back of the units.
WARNING!
Do not use the Battery Backup/LVD option
units connected in parallel, as there is a risk that the potential
current could be higher than the rating of the internal low
voltage disconnect relay.
Otherwise damage to the unit, load, and/or personal injury may
occur if the battery output current through the BAT terminal
exceeds the rating for an individual supply.
CAUTION!
Do not connect power supplies of different output voltage
ratings in parallel, as this may cause damage to equipment or
connected load.