Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
47
of 84
LVD Disconnect Voltage
: Shows the battery voltage when the LVD will
disconnect the battery.
LVD Reconnect Voltage
: Shows the battery voltage when the LVD will
reconnect the battery.
LVD Status
: Shows the status of the LVD (Open or Closed).
Alarm Status
: Shows status of the batteries (Alarm or OK).
4.5.2
SETTINGS & CONTOL
This tab is used to adjust the settings of the BMMD.
WARNING
Always consult battery manufacturer's specifications when
selecting battery type. Incorrect battery type setting may
damage the battery
. If Lithium Ion type battery is selected, an
integrated battery management system (BMS) must be used to
protect the battery cells from inappropriate voltage or current
levels.
Configure Battery
Battery Type:
Configure the Battery Type of the battery used in the
system (Lead Acid or Lithium Ion).
Battery Capacity:
Set the "Battery Capacity" in Ah (50 to 2000 Ah) of
the total battery pack connected to the unit. This value is used by the
unit when estimated Run-time Remaining. The default setting is 100 Ah.