Hybrid Ultra
855-350-050_Rev2.0_Instruction Manual
Page
29
of 84
X
Press Back
X
to return to LDM Settings
screen.
Scroll to highlight the sub-menu to change
(Output Undercurrent).
Press Enter to select.
Scroll to highlight Output to be adjusted.
Press Enter to select.
Use the Up/Down buttons to adjust setting,
press Enter to set value and return to
previous screen. Press Back
X
to return to
previous screen without saving changes.
3.2.5
Alarm Inputs
The Alarm Inputs Status screen displays the status of the four alarm inputs
provided on a unit equipped with the ICM. Use these inputs to monitor
voltage free external contact closures such as door sensors, smoke alarm
outputs or a water sensor.
Other information will be shown depending on the operating state of the unit:
•
Alarm Inputs screen will not be displayed with disabled alarms
•
OK will be displayed when there is no change on the state of the
contacts
•
ALARM will be displayed when a contact activates
Configure the logic of the external contact type selecting Normally Open
(NO) or Normally Closed (NC) to activate the alarm inputs using the GUI
Alarms Settings & Control tab (see Section 4.7.2). The factory default setting
has the alarm inputs disabled.
Press Enter to see the Alarm History log (see
below section for the Alarm History log).