Communications Wiring
This chapter describes wiring for RS-232, RS-422 and RS-485 communications.
Installation Requirements
All equipment connected to the RS-232 ports must be Listed, have an Electronics Industrial
Association (EIA) standard RS-232 communications protocol, and not be installed over a
hazardous location.
RS-232 communication must not exceed 100 feet. RS-232 communication wires must be in a
separate PVC conduit away from any AC wire.
Communications equipment signal wires must also be run in separate rigid PVC or metal
conduit, separate from any power conduit.
24/4 Comm Cable (can be purchased from ICS).
RS-232 COMM Terminal Wiring Diagram
Wiring to be done on the main CPU board.